INSTALLATION | ||
|
|
|
REMOTE CONTROL
The AIR VANTAGE® 500 KUBOTA is equipped with a
When in TOUCH START TIG mode and when a Amptrol is connected to the
When in the DOWNHILL PIPE mode and when a remote control is connected to the
EXAMPLE: When the OUTPUT CONTROL on the welder is set to 200 amps the current range on the remote control will be
In the
The
WARNING
NOTE: When a wire feeder with a built in welding voltage control is connected to the
AUXILIARY POWER RECEPTACLES
Start the engine and set the “IDLER” control switch to the “High Idle” mode. Voltage is now correct at the recepta- cles for auxiliary power. This must be done before a tripped GFCI module can be reset properly. See the MAINTENANCE section for more detailed information on testing and resetting the GFCI module.
The auxiliary power of the AIR VANTAGE® 500 KUBO- TA consists of two 20
The auxiliary power capacity is 13,000 watts Peak, 12,000 Watts Continuous of 60 Hz, single phase power. The auxiliary power capacity rating in watts is equivalent to
The 240 VAC output can be split to provide two separate 120 VAC outputs with a max permissible current of 50 Amps per output to two separate 120 VAC branch cir- cuits (these circuits cannot be paralleled). Output voltage is within ± 10% at all loads up to rated capacity.
The
120 V DUPLEX RECEPTACLES AND GFCI MODULES
A GFCI Module protects the two 120V auxiliary power receptacles.
A GFCI (Ground Fault Circuit Interrupter) is a device to protect against electric shock should a piece of defective equipment connected to it develop a ground fault. If this situation should occur, the GFCI module will trip, remov- ing voltage from the output of the receptacle. If a GFCI module is tripped see the MAINTENANCE section for detailed information on testing and resetting it. A GFCI module should be properly tested at least once every month.
The 120 V auxiliary power receptacles should only be used with three wire grounded type plugs or approved double insulated tools with two wire plugs. The current rating of any plug used with the system must be at least equal to the current capacity of the associated recepta- cle.
NOTE: The 240 V receptacle has two 120 V circuits, but are of opposite polarities and cannot be paralleled.
All auxiliary power is protected by circuit breakers. The 120V has 20 Amp circuit breakers for each duplex recep- tacle. The 120/240V Single Phase and the 240V Three- Phases have a 50 Amp
AIR VANTAGE® 500 KUbOTA