A-7

INSTALLATION

A-7

 

 

 

Take necessary steps to assure load is limited to the capacity of the Commander by installing a 45 amp, 240 VAC double pole circuit breaker. Maximum rated load for each leg of the 240 VAC auxiliary is 45 amperes. Loading above the rated output will reduce output voltage below the allowable -10% of rated volt- age which may damage appliances or other motor- driven equipment and may result in overheating of the Commander 300 engine.

Install a 50 amp 120/240 VAC plug (NEMA Type 14-

50)to the double-pole circuit breaker using No. 6, 4 conductor cable of the desired length. (The 50 amp, 120/240 VAC plug is available in the optional K802R plug kit.)

Plug this cable into the 50 Amp 120/240 Volt recepta- cle on the Commander 300 case front.

Figure A.2 Connection of the Commander 300 to Premises Wiring

240Volt

60 Hz.

3-Wire

Service

240 VOLT

POWER

120 VOLT

COMPANY

120 VOLT

METER

GROUNDED CONDUCTOR

NEUTRAL

BUS

DOUBLE POLE DOUBLE THROW

SWITCH RATING TO BE THE SAME

AS OR GREATER THAN PREMISES

SERVICE OVERCURRENT

PROTECTION.

 

 

45AMP

 

 

240 VOLT

 

 

DOUBLE

50 AMP, 120/240

 

POLE

 

CIRCUIT

VOLT PLUG

240 VOLT

BREAKER

NEMA TYPE 14-50

 

 

GND

N

N

LOAD

PREMISES

DISCONNECT AND

SERVICE

GROUNDOVERCURRENT PROTECTION

50 AMP, 120/240 VOLT

RECEPTACLENOTE: No. 8 COPPER CONDUCTOR CABLE SEE NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

COMMANDER 300

Page 15
Image 15
Lincoln Electric IM700-D manual Power