Lincoln Electric IM931 manual Connection of Ranger 250 LPG to Premises, Gnd

Models: IM931

1 52
Download 52 pages 28.74 Kb
Page 16
Image 16

A-8

INSTALLATION

A-8

 

 

 

CONNECTION OF RANGER 250 LPG TO PREMISES

240Volt

60 Hz.

3-Wire

Service

240 VOLT

POWER

120 VOLT

COMPANY

120 VOLT

METER

GROUNDED CONDUCTOR

NEUTRAL

BUS

N

DOUBLE POLE DOUBLE THROW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LOAD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SWITCH RATING TO BE THE SAME

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AS OR GREATER THAN PREMISES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SERVICE OVERCURRENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROTECTION.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PREMISES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISCONNECT AND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SERVICE

 

 

 

 

 

 

 

 

GROUND

 

 

 

 

40AMP

OVERCURRENT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PROTECTION

 

 

 

 

240 VOLT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DOUBLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

50 AMP, 120/240

 

 

POLE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CIRCUIT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VOLT PLUG

240 VOLT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

BREAKER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NEMA TYPE 14-50

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

N

50 AMP, 120/240 VOLT

RECEPTACLENOTE: No. 6 COPPER CONDUCTOR CABLE SEE NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE

SIZE RECOMMENDATIONS.

WARNING

Only a licensed, certified, trained electrician should install the machine to a premises or residential electrical system. Be certain that:

•The installation complies with the National Electrical Code and all other applicable electrical codes.

•The premises is isolated and no feedback into the utility system can occur. Certain state and local laws require the premises to be isolated before the generator is linked to the premises. Check your state and local requirements.

•A double pole, double throw transfer switch in conjunction with the properly rated double throw cir cuit breaker is connected between the generator power and the utility meter.

RANGER 250 LPG

Page 16
Image 16
Lincoln Electric IM931 manual Connection of Ranger 250 LPG to Premises, Gnd