| INSTALLATION |
|
|
|
|
|
|
| ||||||||
TECHNICAL SPECIFICATIONS - POWER WAVE® S350 |
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
| POWER |
|
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Model | Duty Cycle |
| Input Voltage ± 10% |
|
| Input Amperes |
| Idle Power | Power Factor @ | |||||||||
|
|
|
|
|
|
| (1 Phase in parenthesis) |
|
|
|
| Rated Output | ||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 40% rating |
| 208/230/400*460/575 |
|
| 39/35/19/17/14 |
|
|
|
|
|
|
|
| ||||
|
|
|
|
| 1 |
|
|
|
|
|
|
|
|
| ||||
|
|
| 50/60 Hz |
| (60/67 /NA/NA/NA) |
| 300 Watts Max. | .95 | ||||||||||
|
|
|
|
|
|
|
|
| ||||||||||
|
|
|
|
|
|
|
|
| ||||||||||
| 100% rating |
| (*includes 380V to 413V) |
| 31/28/15/14/11 |
|
| (fan on) |
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
| (60/53/NA/NA/NA) |
|
|
|
|
|
|
|
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
| RATED OUTPUT |
|
|
|
|
|
|
|
|
| ||||
| INPUT |
|
|
| GMAW |
|
|
|
| SMAW |
|
|
|
| ||||
VOLTAGE/PHASE/ | 40%* | 60% | 100% |
| 40%* | 60% | 100% |
| 40% |
| 60% |
| 100% | |||||
FREQUENCY |
|
|
|
|
|
| ||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 300 Amps / 29 Volts |
| 250 Amps / 30 Volts |
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
230/1/50/60 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
| 350 | 320 | 300 |
| 325 | 275 | 250 |
|
|
|
|
|
| ||||
|
|
|
| 350 |
| 325 |
| 300 | ||||||||||
230/3/50/60 |
|
| Amps | Amps | Amps |
| Amps | Amps | Amps |
|
|
| ||||||
|
|
|
| Amps |
| Amps |
| Amps | ||||||||||
|
| 31.5 | 30 | 29 |
| 33 | 31 | 30 |
|
|
| |||||||
|
|
|
| 24 Volts |
| 23Volts |
| 22 Volts | ||||||||||
460/3/50/60 |
|
| Volts | Volts | Volts |
| Volts | Volts | Volts |
|
|
| ||||||
|
|
|
|
|
|
|
|
| ||||||||||
575/3/50/60 |
|
|
|
|
|
|
|
|
| |||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*On 230 Volt / 1 phase inputs the max. rating is at a duty cycle of 30%, except for GTAW processes.
RECOMMENDED INPUT WIRE AND FUSE SIZES 1
INPUT | MAXIMUM | CORD SIZE 3 | TIME DELAY FUSE |
VOLTAGE / PHASE/ | INPUT AMPERE RAT- | AWG SIZES | OR BREAKER 2 |
FREQUENCY | ING AND DUTY CYCLE | (mm2) | AMPERAGE |
|
|
|
|
60A, 100% | 6 (13) | 80 | |
39A, 40% | 8 (10) | 50 | |
230/1/50/60 | 67A, 30% | 4 (16) | 80 |
230/3/50/60 | 35A, 40% | 8 (10) | 45 |
19A, 40% | 12 (4) | 30 | |
460/3/50/60 | 17A, 40% | 12 (4) | 25 |
575/3/50/60 | 14A, 40% | 14 (2.5) | 20 |
|
|
|
|
1. Based on U.S. National electrical Code
2. Also called " inverse time" or "thermal / magnetic" circuit breakers; circuit breakers that have a delay in trip- ping action that decreases as the magnitude of the current increases
3. Type SO cord or similar in 30° C ambient
4. When operating on these inputs, the line cord should be changed to an input conductor of 6 AWG or larger.
POWER WAVE® S350