Advanced Controller Programming (Cont.)

Auxiliary Relay Mode

The Auxiliary Relay has normally open and normally closed contacts. The factory setting disables the Auxiliary Relay. The relay can be set for:

• Maglock: To deactivate a magnetic or solenoid gate lock, the relay

will energize during any pending or actual gate motion (open only).

• M4: To deactivate a magnetic or solenoid gate lock, the relay will

energize during any pending or actual gate motion (open only).

3 seconds after the gate starts to move, the relay will de-energize.

This option is used for higher current solenoid locks.

• Ticket Dispenser: The relay will energize while the gate is moving

in the open direction and at the full open limit, or in an entrapment

condition.

• Strobe: To activate a warning strobe light, the relay will energize

during any pending or actual gate motion (either open or close).

FUNCTION

"AR"

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO SELECT AN OPTION

AUXILIARY

RELAY MODE

OPTIONS

AUXILIARY RELAY DISABLED

AUXILIARY RELAY USED FOR

MAGLOCK CONTROL

AUXILIARY RELAY USED FOR

MAGLOCK OR SOLENOID CONTROL 3 SECOND DELAY TO RE-ENERGIZE

AUXILIARY RELAY USED FOR

TICKET DISPENSER CONTROL

AUXILIARY RELAY USED FOR

WARNING STROBE LIGHT

AUXILIARY RELAY USED FOR

CONNECTION TO ALARM DEVICE

• Alarm: The relay will energize if the gate is manually forced open

from the full closed position.

Reverse Delay Time

The factory default sets the Reverse Delay to 1 second. The operator will wait the length of the delay before reversing direction. This feature will not change the reversal time when the operator is responding to an entrapment condition from an obstruction input or inherent entrapment protection sensor. The Reverse Delay can be set from 1 to 9 seconds. Heaver gates require a longer delay to allow time for the gate to stop.

FUNCTION

 

OPTIONS

 

 

 

"RD"

 

 

 

SET TIMER VALUE

 

 

 

 

 

 

 

 

 

 

 

 

1 TO 9 SECONDS

 

 

 

 

 

 

 

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

REVERSE

DELAY TIME

Brake Delay Time

This function is displayed,but only used in operators with mechanical brakes. The Model VS-GSWG does not have a mechanical brake.

The factory default sets the Brake Delay to no delay (0 seconds). Heavy gates may require delayed braking to allow the gate to slow down before stopping it. The operator can be set to wait the length of the delay after running before applying the brake. The Brake Delay can be set from 0 to 3 seconds.

Constant Pressure Mode

The factory default allows momentary pressure on a control station’s OPEN or CLOSE button to cycle the operator. The controller can be set

FUNCTION

"BD"

BRAKE

DELAY TIME

OPTIONS

SET TIMER VALUE 0 TO 3 SECONDS

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO

SELECT AN OPTION

to require constant pressure on the OPEN, CLOSE, or both buttons to run the operator.

NOTE: If a button is set for constant pressure, and it is released before the operator reaches the open or close limit, the operator will stop the gate at its current position.

Shadow Loop Open Prevention

If the shadow loop is triggered, it always prevents the gate from closing if the Auto Close Timer activates or a CLOSE command is given while the gate is at the full open position.

FUNCTION

"CP"

PRESS UP OR

DOWN TO CYCLE

THROUGH OPTIONS

PRESS ENTER TO SELECT AN OPTION

CONSTANT

PRESSURE MODE

OPTIONS

CONSTANT PRESSURE SET TO OFF (MOMENTARY PRESSURE ON)

OPEN BUTTON SET FOR

CONSTANT PRESSURE

CLOSE BUTTON SET FOR

CONSTANT PRESSURE

OPEN AND CLOSE BUTTONS BOTH SET FOR CONSTANT PRESSURE

The controller can also be set to prevent the gate from opening if the shadow loop is triggered while the gate is at the close limit position. This prevents a swing gate from opening into a vehicle if it’s parked near the gate on the inside.

 

FUNCTION

 

OPTIONS

 

 

 

 

"SP"

 

 

 

STANDARD OPERATION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SHADOW LOOP INHIBITS CLOSING ONLY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPEN INHIBIT ON, SHADOW LOOP INHIBITS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPENING AND CLOSING

 

 

 

 

 

PRESS UP OR

 

 

 

 

 

DOWN TO CYCLE

 

 

 

 

 

THROUGH OPTIONS

 

 

 

 

 

 

 

 

 

 

SHADOW LOOP

PRESS ENTER TO

OPEN PREVENTION

SELECT AN OPTION

 

 

 

 

VS-GSWG Swing Gate Operator Installation Guide

- 15 -

P1250 Revision X6 7-8-2011

 

Page 17
Image 17