Service Manual

1Service (continued)

Display panel parameter access

Table 1C This is a typical example of accessing a parameter, shown for parameter H3, cascade address

BUTTON

OPERATION

DISPLAY

COMMENTS

This example shows how to access parameter H3, cascade address. The first display shown is at the beginning of the menu listings, after entering the installer access code.

 

-

Beginning of menu listings.

 

>A General

 

 

B N/A

 

 

 

 

 

DOWN

Press 1 time to toggle menu listing

 

>C

Data Log

 

 

D

Functions

 

 

 

 

 

 

 

 

>E

WHR Settings

 

DOWN

Press 2 times to toggle menu listing

 

 

 

F

N/A

 

 

 

 

 

 

 

 

>G

N/A

 

DOWN

Press 1 time to toggle menu listing

 

 

 

H

Control Modes

 

 

 

 

 

 

 

 

G

Anti-Cycling

 

DOWN

Press 1 time to select second listing

 

 

 

>H

Control Modes

 

 

 

 

 

 

 

 

 

 

ENTER/RES

Press 1 time to list parameters

 

H2 Contrl Source

 

 

 

 

 

 

 

 

 

 

UP

Press 1 time to select next parameter

H3 Cascade Addr

 

 

Press 1 time to show parameter value

H3 Cascade Addr

ENTER/RES

Member 0001

 

 

UP

Press 1 time to change value

H3 Cascade Addr

(or DOWN)

Member 0002

ENTER/RES Press 1 time to save new value

H3 Cascade Addr

 

ENTER/RES

Press 1 time to return to main menu

>A General

B N/A

 

 

ENTER/RES

Press 1 time to return to normal

WHR:Pre-Purge

operation

OUT:123.7˚F

The caret symbol, ">" highlights the selectable line

The menu toggles to the next two menu options

The menu toggles to the next two menu options

The menu toggles to the next two menu options

The menu toggles to the next two menu options

H2 will flash

H3 will flash

H2 will stop flashing; parameter value will appear

Parameter will increase or decrease, depending on button pressed

H3 will flash

This display example assumes a call for water heating is present