Service Manual

3Troubleshooting

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Water Heater Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

The temperature rise across the heat

• Verify that the system is full of water and that all air

 

exchanger has exceeded the set parameters

has been properly purged from the system.

 

 

 

for the water heater.

• Verify that the water heater is piped properly into the

 

 

heating system. Refer to Section 6 - System Piping

 

 

of the Armor Water Heater Installation and Operation

 

 

Manual for the proper piping methods for the Armor

 

 

water heater.

 

 

• Check for 120 VAC to the water heater pump motor on

 

 

a call for heat. If voltage is not present, check the

 

 

wiring back to the main control board. Replace the

 

 

main control board if necessary.

 

 

• If 120 VAC is present on a call for heat and the water

 

 

heater pump is not operating, replace the pump.

 

 

• Verify that the water heater pump is set to the proper

Temp O/Shoot

 

speed or that the pump is the proper size. Reference

 

Section 6 - System Piping of the Armor Water Heater

(continued)

 

Installation and Operation Manual for water heater

 

 

pump specifications.

 

 

 

 

Outlet water temperature has exceeded the

• Verify that the system is full of water and that all air

 

maximum outlet water temperature.

has been properly purged from the system.

 

 

 

 

• Verify that the water heater is piped properly into the

 

 

heating system. Refer to Section 6 - System Piping

 

 

of the Armor Water Heater Installation and Operation

 

 

Manual for the proper piping methods for the Armor

 

 

water heater.

 

 

• Check for 120 VAC to the water heater pump motor on

 

 

a call for heat. If voltage is not present, check wiring

 

 

back to the main control board. Replace the main

 

 

control board if necessary.

 

 

• If 120 VAC is present on a call for heat and the water

 

 

heater pump is not operating, replace the pump.

 

 

• Replace the main control board.

 

 

 

 

External control is cycling too often.

• Check set point of the external control.

 

 

Rem Ctrl Flt

 

• Check the wiring between the external control and the

 

 

unit.

 

 

• Replace the control.

 

 

 

Parameters

After downloading parameters from a laptop,

 

Progr

• Press the ENTER/RESET button on the SMART

(will require a manual

the main control board must be reset.

SYSTEM display panel.

 

reset once the condition

 

 

has been corrected. Press

 

 

the RESET button on the

 

 

SMART SYSTEM display

 

 

to reset.)

 

 

 

 

 

30

Page 30
Image 30
Lochinvar 150 - 800 service manual Rem Ctrl Flt, Parameters, Progr