Table 3D Troubleshooting Chart - Noisy System

Service Manual

3Troubleshooting

Table 3D Troubleshooting Chart - Noisy System

FAULT

 

 

 

CAUSE

 

 

 

CORRECTIVE ACTION

 

 

 

 

 

 

 

 

 

 

 

 

- Supply gas problem. Natural gas pressures

 

 

 

 

 

 

 

 

should be

between

4

inches

w.c.

and

• Refer to Section 7 - Gas Connections

of the Armor

 

14

inches

w.c.

LP

gas

pressures should

Water Heater Installation and Operation Manual for

 

be

between

8

inches

w.c.

and

detailed information concerning the gas supply.

 

 

 

14 inches w.c.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Refer to the Gas Valve Adjustment Procedure on

 

 

 

 

 

 

 

 

 

pages 33-34 of this manual for the proper gas valve

 

- Gas/air mixture problem.

 

 

 

setting.

Verify that the vent/air intake lengths

do

not

 

 

 

 

exceed the maximum listed in the General Venting

 

 

 

 

 

 

 

 

 

Noisy

 

 

 

 

 

 

 

 

section of the Armor Water Heater Installation and

 

 

 

 

 

 

 

 

Operation Manual.

 

 

 

 

Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Refer to page 19 in this manual for the burner removal

 

 

 

 

 

 

 

 

 

 

- Dirty/damaged burner.

 

 

 

and inspection procedure.

Clean or replace the burner

 

 

 

 

 

 

 

 

 

as necessary.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Refer to Section 6 - System Piping of the Armor Water

 

- Low water flow through the heat exchanger.

Heater Installation and Operation Manual for minimum

 

 

 

 

 

 

 

 

 

flow rates.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Air in the piping system.

 

 

 

• Properly purge all air from the piping system.

 

 

 

 

 

 

 

 

 

 

- Low system water pressure.

 

 

• Verify system pressure is a minimum of 12 PSI.

 

 

 

 

 

 

 

 

 

 

 

 

 

- Blown fuse.

 

 

 

 

 

• Replace fuse F5 on the control board, see page 21 of

 

 

 

 

 

 

this manual.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No Pump

 

 

 

 

 

 

 

 

 

 

 

- Faulty pump.

 

 

 

 

 

• Replace pump.

 

 

 

 

Operation

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Faulty pump relay.

 

 

 

 

• Replace pump relay.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Internal fault on control board.

 

 

• Replace main control board.

 

 

 

 

 

 

Relief Valve

- System pressure exceeds relief valve

• Lower the system pressure below the 150 PSI rating of

Opening

setting.

 

 

 

 

 

 

the supplied relief valve.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Check the wiring connections to switch. Wires should

 

 

 

 

 

 

 

 

 

be connected to the common and normally closed

 

 

 

 

 

 

 

 

 

terminals.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Air intake lengths exceed the maximum allowed

APS

 

 

 

 

 

 

 

 

lengths. Refer to Section 3 - General Venting of the

 

 

 

 

 

 

 

 

Armor Water Heater Installation and Operation Manual

Open

 

 

 

 

 

 

 

 

for proper lengths.

 

 

 

 

(will require a

 

 

 

 

 

 

 

 

• Check

for

obstruction

or blockage

in

the

air

manual reset once the

 

 

 

 

 

 

 

 

intake pipes or at terminations.

 

 

 

condition has been

Air pressure switch contacts are open.

 

• Check reference hoses connected to the air pressure

corrected. Press the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

switch for blockage or obstruction.

 

 

 

RESET button on the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Inspect the burner. Reference page 19 of this manual

SMART SYSTEM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

for removal

and cleaning procedures.

Replace if

display to reset.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

necessary.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Inspect the heat exchanger. Reference page 20 of this

 

 

 

 

 

 

 

 

 

manual for removal and cleaning procedures. Replace

 

 

 

 

 

 

 

 

 

if necessary.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

• Faulty air pressure switch. Replace switch.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 