SH off-on differential (SH off/on df)
The SH
Drop of inlet temp before ending
The control will bypass the
Offset HW setpoint to end HW demand
When heating an indirect hot water tank (heat maker), the tank temperature (or inlet temperature if a tank sensor is not used) must rise above the tank setpoint (parameter 4AS) by this amount before the HW heat demand will end. This parameter can be changed by accessing parameter 4AG. The temperature range of this parameter is 0° to 54°F (30°C). The default setting is 0°.
Outdoor air shutdown temp (Out SD Setp)
When the outdoor air temperature rises above this point, the control will inhibit all SH demands (HW demands will still be active). This parameter can be changed by accessing parameter 4AH. The temperature range of this parameter is 0°F to 120°F (99°C). The default value is 80°F (27°C).
OA shutdown differential (Out SD df)
This is the number of degrees below parameter 4AH the outdoor air temperature must go before the boiler will again respond to an SH demand. This parameter can be changed by accessing parameter 4AI. The temperature range of this parameter is 0°F to 90°F (50°C). The default value is 10°F (5°C).
Shift OA reset curve (Shift Air Reset)
The Shift Heat Curve shifts the actual setpoint above or below the calculated setpoint by the number of degrees in this parameter. This parameter can be changed by accessing parameter 4AJ. The temperature range of this parameter is
Night setback temperature (NSB Setp)
Once the internal clock has been set correctly, the night setback feature can be used to program a lower water temperature setpoint for space heating. This parameter can be changed by accessing parameter 4AK. The temperature range for this parameter is 32°F (0°C) to 140°F (60°C). With a setting of 32°F (0°C) the feature is turned off. The default value will be 32°F (0°C).
SH turn-off differential cascade (Casc off df)
The SH
SH off-on differential cascade (Casc off/on df)
The SH
SH anti-cycling time (Anti-C t)
Once a SH demand has been satisfied, a set amount of time must elapse before the control will respond to a new SH demand. This helps prevent short cycling of the boiler. The control will inhibit the new heat demand and
Max service time (Max Serv t)
The service mode allows the installer to set the unit to a fixed firing rate for the purpose of combustion analysis. The delay sets the length of time the boiler will stay in the service mode if no keys have been pressed before going back to its original state. This parameter can be changed by accessing parameter 4AP. The time range of this parameter is 0 minutes to 40 minutes. The default value is 20 minutes.
Tank setpoint temp
This setting is applied to the tank sensor (when connected). It is used to start and stop the HW call for heat. This setting can be changed by accessing parameter 4AS. The temperature range is 60°F (15.5°C) to 190°F (87.5°C). The default setting is 120°F (49°C).