1 Service
Figure 1-1_Outdoor Air Reset Curve
Outdoor air reset (boiler only)
Outdoor air reset operation
When the outdoor air sensor is installed, the control will calculate the water temperature setpoint based on the outdoor air temperature. As the outdoor air temperature drops, the water temperature setpoint increases. This feature allows the unit to be more efficient in periods of mild weather, see FIG.
Minimum air temperature
When the outdoor air temperature drops to this point, the water temperature will be at its maximum setting (FIG.
Maximum air temperature
When the outdoor air temperature rises to or above this point, the water temperature will be at its minimum setting (FIG.
Maximum SH setpoint
When the outdoor temperature drops to its minimum setting (F1) the water temperature setpoint will be at this value, if the SH setpoint is set higher (FIG.
Minimum SH setpoint
When the outdoor temperature rises to or above its maximum setting (F2) the water temperature will be at this value (FIG.
Outdoor air shutdown
When the outdoor temperature rises above this point, the control will block all SH demands (DHW demands will still be active). The temperature range of this parameter is 32°F (0°C) to 122°F (50°C). The default value is 80°F (27°C).
20