Lochinvar 402 - 2072 Fault, Cause, Corrective Action, Troubleshooting, No Display, No Burner

Models: 402 - 2072

1 44
Download 44 pages 18.25 Kb
Page 34
Image 34
Table 3A Troubleshooting Chart - No Display

Copper-fin II/IIE Boiler and Water Heater Service Manual

3 Troubleshooting

Table 3A Troubleshooting Chart - No Display

FAULT

CAUSE

 

CORRECTIVE ACTION

 

 

 

 

 

 

 

 

 

 

Check external line switch, fuse, or breaker.

 

 

 

 

• Check position of ON/OFF switch. Turn switch to the

 

- No 120 VAC supplied to unit.

 

ON position.

 

 

 

 

 

• Check 120 VAC through the ON/OFF switch.

No

 

 

 

voltage through switch, replace switch.

 

 

 

 

 

 

No Display

 

• Check wiring harness connection between the display

- Bad wiring connection.

 

board and the main control board. Connect the harness

 

 

 

at both points.

 

 

 

 

 

 

 

 

 

- Blown fuse.

Replace fuse F6 on the main control board,

see

 

 

FIG. 3-1 on page 33 of this manual.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

- Bad display board.

Replace board.

 

 

 

 

 

 

 

 

 

 

 

- Bad main control board.

Replace main control board.

 

 

 

 

 

 

 

 

 

 

 

- Main control board temperature setpoint

Review temperature setting.

 

 

 

 

satisfied.

 

 

 

 

 

 

- Remote thermostat satisfied.

Review remote thermostat setting.

 

 

 

No Burner

 

 

 

 

 

 

- Outside air temperature above Warm

Check location of outside air sensor.

Check

Operation

 

Weather Shutdown (WWSD) setpoint for

 

resistance of outdoor air sensor and compare to Table

 

main control board.

 

3C on page 35 of this manual.

 

 

 

 

 

 

 

 

 

 

 

- Unit locked out on fault.

Consult display for specific fault.

Refer

to

fault

 

 

descriptions on pages 37 - 43 of this manual for

 

 

 

 

 

 

corrective actions.

 

 

 

 

 

 

 

 

 

 

Unit Does

- Boiler controlled by BMS.

 

 

 

 

 

 

• Check BMS parameter settings.

Optional PC

 

Not Stage to

- Outlet temperature too high.

 

software required.

 

 

 

100%

 

 

 

 

 

- Delta T too high.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FAULT 34 CAUSE

Page 34
Image 34
Lochinvar 402 - 2072 Fault, Cause, Corrective Action, A Troubleshooting Chart - No Display, No Burner, Operation, 100%