Lochinvar 402 - 2072 service manual Parameter table B - Water Heater Operation, Service continued

Models: 402 - 2072

1 44
Download 44 pages 18.25 Kb
Page 15
Image 15
Parameter table B - Water Heater Operation

Copper-fin II/IIE Boiler and Water Heater Service Manual

1 Service (continued)

Parameter table B - Water Heater Operation

Table 1E_This table lists SMART SYSTEM control module parameters and where to access them for water heater operation ONLY

CONTROL ANTI- DHWDATA TEMP. CASCADE MODES CYCLING SETTINGS FUNCTIONS LOGGING SETTINGS GENERAL

Menu

Sub

Description

See

User Access

Installer Access

Item

Page

Display

Modify

Display

Modify

 

 

 

1

User Code

17

Yes

Yes

Yes

Yes

 

2

Date and Time

17

Yes

Yes

Yes

Yes

A

3

Software Version (Software Ver)

17

Yes

No

Yes

Yes

4

Temperature Units (Temp Units)

17

Yes

Yes

Yes

Yes

 

 

5

DHW Night Setback Offset (DHW NSB Temp)

17

Yes

Yes

Yes

Yes

 

6

DHW Night Setback Times (DHW NSB Time)

17

Yes

Yes

Yes

Yes

B

1

Manual Reset High Limit (Man Res Hi Lim)

18

Yes

Yes

Yes

Yes

 

1

Hours Running DHW (Hours Run DHW)

18

No

No

Yes

Yes

C

 

 

 

 

 

 

 

2

Ignition Attempts (Ign Attempts)

18

No

No

Yes

Yes

 

 

 

 

 

 

 

 

 

3

Last 10 Lockouts

18

No

No

Yes

Yes

 

1

Clear Error Log (Clr Error Log)

18

No

No

Yes

Yes

 

2

Service Mode Delay (Service Delay)

18

No

No

Yes

Yes

 

3

Display Timeout (Display Time)

18

No

No

Yes

Yes

D

4

Bypass Valve Time (Bypass V Time)

18

No

No

Yes

Yes

 

5

Freeze Protection Pump On (Freeze Pump)

19

No

No

Yes

Yes

 

6

Freeze Protection Burner On (Freeze Burn)

19

No

No

Yes

Yes

 

7

Freeze Protection Differential (Freeze Differ)

19

No

No

Yes

Yes

 

1

Tank Setpoint

19

Yes

Yes

Yes

Yes

 

 

 

 

 

 

 

 

E

2

DHW Tank Offset (DHW Tank Offs)

19

No

No

Yes

Yes

 

3

DHW Tank Differential (DHW Tank Diff)

19

No

No

Yes

Yes

 

1

Anti-cycle Time (Anti Cycl Tm)

21

No

No

Yes

Yes

F

2

Anti-cycle Override Differential (Override Diff)

21

No

No

Yes

Yes

3

On/Off Delay

21

Yes

Yes

Yes

Yes

 

 

4

Next On Delay

21

Yes

Yes

Yes

Yes

 

1

Enable Input (Active / Inactive)

22

No

No

Yes

Yes

 

2

BMS Input (Active / Inactive)

22

No

No

Yes

Yes

G

3

Cascade (Active / Inactive)

22

No

No

Yes

Yes

 

4

ModBus (Active / Inactive)

22

No

No

Yes

Yes

 

5

ModBus Timeout (ModBus Time)

22

No

No

Yes

Yes

 

1

Boiler Address (Blr Adress)

23

No

No

Yes

Yes

H

 

 

 

 

 

 

 

2

Maximum Cascade Setpoint (Max Casc Stpt)

23

Yes

Yes

Yes

Yes

 

 

 

 

 

 

 

 

 

Manual background 15 Manual background

Page 15
Image 15
Lochinvar 402 - 2072 service manual Parameter table B - Water Heater Operation, Service continued