Lochinvar 402 - 2072 Description, Troubleshooting continued, Fault, Corrective Action, Lwco

Models: 402 - 2072

1 44
Download 44 pages 18.25 Kb
Page 37
Image 37
DESCRIPTION

Copper-fin II/IIE Boiler and Water Heater Service Manual

3 Troubleshooting (continued)

Table 3E Troubleshooting Chart - Fault Messages Displayed on Operator Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

- Either the optional manual reset low gas

• Reset the pressure switches.

 

pressure switch or the optional manual reset

 

 

high gas pressure switch tripped.

• Measure the supply gas pressure to determine

Gas Pressure SW

 

cause of failure. Refer to the Gas Connections

- Models 992 - 2072 (natural gas) - Automatic

Section of the Installation and Operation Manual for

(Will require a manual

Reset Low Gas is open.

detailed information concerning the gas supply.

reset once the condition

 

 

has been corrected.)

 

• Correct the supply gas pressure if necessary.

 

 

Flow Switch/

Either the flow switch or the optional low

• Check pump operation on a call for heat.

water cutoff is not making.

 

LWCO

 

• Check for closed valves or obstructions in the

(Lockout will reset

 

water piping.

automatically after

 

 

5 minutes or may be

 

• Verify system is full of water and all air has been

reset immediately once

 

purged from the system.

condition has been

 

 

corrected. Press the

 

 

RESET button on the

 

 

SMART SYSTEM display

 

 

to reset.)

 

 

 

 

 

Flame Sequence

The flame detector circuit is seeing a flame

• Check supply voltage for proper polarity.

signal while the gas valve is de-energized.

 

(Will require a manual

 

• Check that the gas valve is closed.

reset once the condition

 

 

has been corrected. Press

 

• Check external wiring for voltage feedback.

the RESET button on the

 

 

SMART SYSTEM display

 

• Check the internal wiring for bad connections.

to reset.)

 

 

 

 

• Replace main control board.

 

 

 

 

The main control board has received a call

• The control board will release the call for heat after

 

for heat too quickly after the previous call for

a set time period.

Anti-cycling

heat has ended.

• The control board will release the call for heat if the

 

 

 

 

 

outlet temperature drops too quickly.

Gas Pressure SW 37 Flow Switch/

Page 37
Image 37
Lochinvar 402 - 2072 Description, Troubleshooting continued, Fault, Corrective Action, Flow Switch, Lwco, Flame Sequence