Lochinvar 402 - 2072 Troubleshooting, Fault, Description, Corrective Action, Temp O/Shoot

Models: 402 - 2072

1 44
Download 44 pages 18.25 Kb
Page 42
Image 42
Temp O/Shoot

Copper-fin II/IIE Boiler and Water Heater Service Manual

3 Troubleshooting

Table 3E (continued from previous page) Troubleshooting Chart - Fault Messages Displayed on Operator Interface

FAULT

DESCRIPTION

CORRECTIVE ACTION

 

 

 

 

The temperature rise across the heat

• Verify that the system is full of water and that all air

 

exchanger has exceeded the set parameters

has been properly purged from the system.

 

for the appliance.

• Verify that the appliance is piped properly into the

 

 

 

 

heating system. Refer to the Water Connections

 

 

Section of the Installation and Operation Manual for the

 

 

proper piping methods.

 

 

• Check for 120 VAC to the pump motor on a call

 

 

for heat. If voltage is not present, check the wiring

 

 

leading to the main control board. Replace the main

Temp O/Shoot

 

control board if necessary.

 

• If 120 VAC is present on a call for heat and the

(Lockout will reset

 

automatically after 5

 

pump is not operating, replace the pump.

minutes or may be

 

 

 

 

reset immediately once

Outlet water temperature has exceeded the

• Verify that the system is full of water and that all air

condition has been

maximum outlet water temperature.

has been properly purged from the system.

corrected. Press the

 

 

RESET button on the

 

• Verify that the appliance is piped properly into the

SMART SYSTEM display

 

system. Refer to the Water Connections Section of

to reset.)

 

the Installation and Operation Manual for the proper

 

 

piping methods.

 

 

• Check 120 VAC to the pump motor on a call for heat.

 

 

If voltage is not present, check wiring leading to the

 

 

main control board. Replace the main control board

 

 

if necessary.

 

 

• If 120 VAC is present on a call for heat and the pump

 

 

is not operating, replace pump.

 

 

• Replace the main control board.

 

 

 

 

 

• Check setpoint of the external control.

Rem Ctrl Flt

External control is cycling too often.

• Check the wiring between the external control and

 

the unit.

 

 

 

 

• Replace the control.

 

 

 

Parameters Progr

 

 

(Will require a manual

 

• Press the ENTER/RESET button on the Smart

reset once the condition

After downloading parameters from a laptop,

has been corrected. Press

the main control board must be reset.

System display panel.

the RESET button on the

 

 

SMART SYSTEM display

 

 

to reset.)

 

 

 

 

 

Rem Ctrl Flt 42 Parameters Progr