3 General venting (continued)

Stainless steel air intake/vent connections Figure 3-11Near Boiler Stainless Steel Venting Model 286

1. Combustion Air Intake Connector (FIG. 3-11) - Used to provide combustion air directly to the unit from outdoors. A fitting is provided on the unit for final connection. Combustion air piping must be supported per guidelines listed in the National Mechanical Code, Section 305, Table 305.4 or as local codes dictate.

2. Vent Connector (FIG. 3-11) - Used to provide a passageway for conveying combustion gases to the outside. A transition fitting is provided on the unit for final connection. Vent piping must be supported per the National Building Code, Section 305, Table 305.4 or as local codes dictate.

 

 

 

 

 

 

 

 

 

 

 

3" S.S. ADAPTER

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3" S.S. INTERMEDIATE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(FOR SAF-T VENT ONLY)

 

Table 3B Approved Stainless Steel Terminations and Adapters

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ProTech

 

Heat Fab

 

 

 

 

 

Z Flex

 

Model

 

FasNSeal

 

Saf-T Vent

 

 

 

 

 

Z-Vent

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Boiler

Flue

Intake

Boiler

Intermediate

Flue

Intake

Boiler

Flue

 

Intake Air

 

 

 

Air

Air

 

 

Adapter

Termination

Adapter

Adapter

Termination

Adapter

Termination

 

Termination

 

Termination

Termination

 

81 - 211

300715

FSBS3

303889

KB80210

9353BUREZ-1*

9392

9314TERM

2SVSLA03

2SVSTP03

 

2SVSTEX0390

 

 

FSRC3(R.C)

 

 

 

5300CI

 

 

 

 

 

2SVSRCX03

 

 

286

F303759

FSBS4

FSAIH04

KB285600

9454BUREZ-1*

9492

9414TERM

2SVSLA04

2SVSTP04

 

2SVSTEX0490

 

 

FSRC4(R.C.)

303888

 

 

5400CI

 

 

 

 

 

2SVSRCX04

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*= This adapter must be used in addition to the boiler adapter for Saf-T vent pipe as shown in FIG. 3-11, unless approved vent other than standard diameter is used. Consult a Heat Fab representative for questions.

The Knight boiler uses model specific combustion air intake and vent piping sizes as detailed in Table 3C below.

Minimum / Maximum allowable combustion air and vent piping lengths are as follows:

Table 3C Air Intake/Vent Piping Sizes

 

Model

 

Air Intake

Vent

 

81 - 211

 

3 inches

3 inches

 

286

 

4 inches

4 inches

 

 

Increasing or decreasing combustion air

 

NOTICE

 

or vent piping is not authorized.

Combustion Air = 12 equivalent feet minimum / 100 equivalent feet maximum

Vent = 12 equivalent feet minimum / 100 equivalent feet maximum

When determining equivalent combustion air and vent length, add 5 feet for each 90° elbow and 3 feet for each 45° elbow.

EXAMPLE: 20 feet of PVC pipe + (4) 90° elbows + (2) 45° elbows + (1) concentric vent kit (CVK3003) = 49 equivalent feet of piping.

NOTICE

The appliance output rating will reduce by

up to 1.5% for each 25 feet of vent length.