Installation & Operation Manual

4 Sidewall direct venting

Vent/air termination – sidewall

Figure 4-1APVC/CPVC Sidewall Termination of Air

￿WARNING

￿WARNING

￿WARNING

NOTICE

Follow instructions below when determining vent location to avoid possibility of severe personal injury, death, or substantial property damage.

A gas vent extending through an exterior wall shall not terminate adjacent to a wall or below building extensions such as eaves, parapets, balconies, or decks. Failure to comply could result in severe personal injury, death, or substantial property damage.

Do not connect any other appliance to the vent pipe or multiple boilers to a common vent pipe. Failure to comply could result in severe personal injury, death, or substantial property damage.

Installation must comply with local requirements and with the National Fuel Gas Code, ANSI Z223.1 for U.S. installations or CSA B149.1 for Canadian installations.

and Vent

TO BOILER

INTAKE AIR

CONNECTION

FROM BOILER

VENT PIPE

CONNECTION

12"

POSSIBLE ORIENTATIONS

MIN

TO

OVER-

HANG

VENT / AIR

TERMINATION

12"

MIN

GRADE OR

SNOW LINE

Table 4A Sidewall Vent Kits

Model

Kit Number

Vent Size

 

 

 

81 - 211

KIT30045

3 inch vent

Determine location

Locate the vent/air terminations using the following guidelines:

1.The total length of piping for vent or air must not exceed the limits given in the General Venting Section on page 19 of this manual.

286

KIT30046

4 inch vent

If using the alternate sidewall termination:

3.The air piping must terminate in a down-turned elbow as shown in FIG. 4-1B. This arrangement avoids recirculation of flue products into the combustion air

stream.

2.You must consider the surroundings when terminating 4. The vent piping must terminate in an elbow pointed

the vent and air:

outward or away from the air inlet, as shown in FIG. 4-1B.

a.

Position the vent termination where vapors will

￿ WARNING

Do not exceed the maximum lengths of the

 

not damage nearby shrubs, plants or air

 

conditioning equipment or be objectionable.

 

outside vent piping shown in

FIG. 4-1B.

 

 

Excessive length exposed to

the outside

b.

The flue products will form a noticeable plume as

 

 

could cause freezing of condensate in the

 

they condense in cold air. Avoid areas where the

 

 

 

vent pipe, resulting in potential boiler

 

plume could obstruct window views.

 

 

 

shutdown.

 

c.

Prevailing winds could cause freezing of

 

 

Figure 4-1BAlternate PVC/CPVC Sidewall Termination

 

condensate and water/ice buildup where flue

 

products impinge on building surfaces or plants.

of Air and Vent w/Field Supplied Fittings

 

d.

Avoid possibility of accidental contact of flue

 

 

 

 

products with people or pets.

 

 

 

e.

Do not locate the terminations where wind eddies

 

 

 

 

could affect performance or cause recirculation,

 

 

 

 

such as inside building corners, near adjacent

 

 

 

 

buildings or surfaces, window wells, stairwells,

 

 

 

 

alcoves, courtyards, or other recessed areas.

 

 

 

￿WARNING

Sidewall vent and air inlet terminations must terminate in the same pressure zone.

f.Do not terminate above any door or window. Condensate can freeze, causing ice formations.

g.Locate or guard vent to prevent condensate damage to exterior finishes.

Page 21
Image 21
Lochinvar 81 - 286 operation manual Sidewall direct venting, Vent/air termination sidewall, Determine location

81 - 286 specifications

Lochinvar 81 - 286 is a state-of-the-art boiler recognized for its efficiency and reliability in both residential and commercial applications. This high-performance heating solution is designed to meet the diverse needs of users while adhering to modern environmental standards.

One of the standout features of the Lochinvar 81 - 286 is its advanced condensing technology. This allows the unit to harness more heat from the combustion gases, significantly boosting its thermal efficiency. With an impressive efficiency rating of over 95%, users can expect lower energy bills and reduced carbon emissions, making this boiler an environmentally friendly choice.

The Lochinvar 81 - 286 incorporates a robust stainless steel heat exchanger that guarantees durability and longevity. This corrosion-resistant material not only prolongs the unit's life but also ensures consistent performance over time. Additionally, the heat exchanger’s design facilitates optimal heat transfer, further enhancing the boiler's efficiency.

In terms of control, the Lochinvar 81 - 286 features a user-friendly control interface that simplifies operation. The boiler is equipped with advanced modulation capabilities, allowing it to adjust its output based on real-time heating demands. This responsiveness reduces energy waste and optimizes comfort levels within the space it serves.

The boiler also supports a variety of installation configurations, providing flexibility for different building layouts. Its compact design allows for easy installation in restricted spaces, while versatile venting options facilitate integration into various systems.

Safety is a paramount consideration in the design of the Lochinvar 81 - 286. The unit comes with integrated safety features such as a built-in diagnostic system that alerts users to any potential issues before they escalate. This proactive technology helps in maintaining seamless operation and reducing downtime.

Finally, the Lochinvar 81 - 286 is compliant with the latest regulations and industry standards, ensuring that it meets the expectations of both consumers and environmental agencies. With its impressive combination of efficiency, durability, and advanced technology, the Lochinvar 81 - 286 stands out as a top choice for anyone seeking a high-performance heating solution. This boiler not only addresses the immediate needs of heating but also supports long-term sustainability initiatives, proving to be a wise investment for the future.