HARMONY SPECIFICATIONS

Input Voltage

120VAC

Power Consumption

30VA

Lead Stage Rotation

 

Manual

 

First On/First Off

 

Automatically

Every hour to every 7 days

Output Types

4-20mA, or

Voltage

0-5V, 0-10V, 1-5V, or 2-10V

Stage Modes

Off, Auto, On, Standby, Manual

Output Contacts

5 SPST

Output Rating

6A resistive, 1/3HP

Operating Ambient Temperature

20 to 120°F

Enclosure

NEMA -1

Dimensions

12-3/4” x 12-3/4” x 4-5/8"

Temperature Accuracy

± 1°F (1°C)

Temperature Display

Field select °F or °C

Temperature Range

-30 to 250°F (-35 to 120°C)

Ignition Start Point

1 to 50%

Modulation Start Point

50 to 100%

Operating Mode

Normal or Process

Purge Delay

1.0 to 10.0 minutes

Lag Stage Delay

0 to 60 minutes

System Run On Delay

0 to 30 minutes

Standby Time

0 to 60 minutes

Setback

0 to 75°F (0 to 42°C)

Last Stage Hold

0 to 30°F (0 to 30°C)

Shutdown Input

Dry Contact Only

System Prove Input

Dry Contact Only

Boiler Active Inputs

Dry Contact Only

4-20mA External Input

 

Only Available on Temperature Units

Harmony can source or sink current