SYSTEM STARTUP
ADJUST | Press to | ||
>Setback |
|
| select |
|
| ||
| PRESS TO SELECT Setback | ||
ADJUST | or turn | ||
>Setback |
|
| to scroll |
| PRESS TO SELECT | down | |
ADJUST | Press to | ||
Setback |
|
| select |
| PRESS TO SELECT | EMS |
IMPORTANT: Do not select
- OUTPUT TYPE A&B | - | ADJUST | Press to |
|
| select | |
| PRESS TO SELECT | ||
|
| ||
|
|
|
|
- OUTPUT TYPE A&B | - | ADJUST | or turn |
|
| ||
|
| to scroll | |
| PRESS TO SELECT | ||
|
| down | |
|
|
|
|
- OUTPUT TYPE A&B | - | ADJUST | Press to |
|
| select | |
| PRESS TO SELECT | ||
|
| new | |
|
|
| |
- OUTPUT TYPE C&D | - | Repeat | |
| process for | ||
| Stages C&D | ||
| |||
|
|
|
EMS INPUT
Default - Setback
Not available for Reset Sensor Types
Setback
•This default setting allows the Set Point to be adjusted either manually at the panel, or by a Visual Gold upgrade for remote communications.
•If desired, a dry contact switch can be wired across the EMS INPUT terminals SIGNAL and SHIELD to allow the panel to hold a lower temperature Set Point when less load is required. To adjust the amount of Setback, see pg. 19.
•When selecting Setback, there is no requirement for any wiring across the EMS INPUT terminals. DO NOT select
External Set Point (4-20mA EMS-Control)
•For this option, an EMS system must provide a
•An active signal must be wired into the EMS Harmony terminals. If the Harmony does not receive a signal between 3.9mA and 20.1mA, it will NOT activate any stages.
•If your system meets the above two criteria, see pg. 28 to complete the
SELECTING THE OUTPUT TYPE
•The Harmony has two output cards, one for stages A & B, and one for stages C & D.
•Both output cards must be programmed for the appropriate mode of operation.
•Outputs can be configured for
•Check the modulating motor to determine its control requirements.
•Select the appropriate Output Type for stages A & B. The Harmony will then automatically bring up the screen for stages C & D.
•Select the appropriate Output Type for stages C & D.
•If different types of burners are being used, stages C & D can be selected to have a different Output Type than stages A & B.
-MODULATING MODE >NORMAL
PARALLEL
-MODULATING MODE NORMAL
>PARALLEL
-MODULATING MODE NORMAL
>PARALLEL
ADJUST
PRESS TO SELECT
ADJUST
PRESS TO SELECT
ADJUST
PRESS TO SELECT
Press to
select
Normal
or turn
to scroll
down
Press to
select Parallel
SELECTING THE MODULATING MODE Default - Normal
•Most boilers run more efficiently as their modulation increases. Therefore, for most systems, it is more energy efficient to run one boiler in high than several boilers at lower modulation. If your system is of this type, select Normal.
•There are some systems were it may be more energy efficient to run several units at lower modulation than one at high. If that is the case select Parallel.
12