Lochinvar Harmony Output Wiring, WIRING TO 4-20MA MODULATING MOTORS, Installation, Voltage

Models: Harmony

1 32
Download 32 pages 16.53 Kb
Page 9
Image 9
Wiring the Stage Outputs

3 4 5 6 7 8 9 10 11 12

C

SYS

A

B

C

D

 

 

OPERATING LIMIT

 

 

 

OUTPUTS

 

 

 

 

Limit Circuit

Wiring the Stage Outputs

Each Stage output (A through D) has one Normally Open (N.O.) relay contact.

The N.O. contacts are dry contacts only. They do not source any voltage.

Each N.O. contact is capable of switching 6A resistive at 120VAC.

Total output of all stages, including the SYS, must not exceed 15A.

Wire the N.O. relay contacts in series with the boiler’s limit circuit.

Class 1 voltages must enter the enclosure through a different opening from any Class 2 voltage wiring.

INSTALLATION

Typical for each stage

4-20 mA

MODULATION OUTPUTS

Common

Common

Common

Common

mA

 

mA

 

mA

 

mA

 

 

 

 

 

 

 

 

 

 

 

C1

C2

C3

C4

C5

C6

C7

C8

C9

C10 C11 C12

A

B

C

D

-+

4 - 20mA Motor

WIRING TO 4-20 MA MODULATING MOTORS

The Harmony can be equipped to operate up to four 4-20 mA modulating motors.

To program the control for 4-20 mA output, see System Startup settings, pg. 12.

Apply the supplied label marked 4-20 mA below the output termi- nals.

The output boards are connected on the rear of the panel.

The pair of outputs A and B are controlled by a one output board. The pair of outputs C and D are controlled by a second output board.

The Harmony sources 24VDC excitation voltage for the 4-20mA signal.

Wire as shown below:

 

 

Common

mA Source (+)

 

 

 

 

 

Stage A

C1

C2

Harmony

Stage B

C4

C5

Sources

 

 

 

Stage C

C7

C8

Current

 

Stage D

C10

C11

 

 

 

 

OUTPUT WIRING

Voltage

MODULATION OUTPUTS

V+ V+ V+ V+

GND

GND

GND

GND

 

 

 

 

 

 

 

 

C1

C2

C3

C4

C5

C6

C7

C8

C9

C10 C11 C12

 

A

 

 

 

B

 

 

 

C

 

 

 

D

 

 

 

 

 

 

 

 

 

0- 5 V

 

0- 5 V

 

0- 5 V

 

0- 5 V

 

or

 

 

or

 

 

or

 

 

or

0-10V

 

0-10V

 

0-10V

 

0-10V

Motor

 

Motor

 

Motor

 

Motor

 

A

 

 

B

 

 

C

 

 

D

WIRING TO VOLTAGE MODULATING MOTORS

The Harmony can be equipped to operate up to four 0-5 V, 0-10V, 1- 5V, or 2-10V modulating motors.

Apply the supplied label marked Voltage below the output terminals.

The output boards are connected on the rear of the panel.

To select the range, 0-5V, 0-10V, 1-5V or 1-10V, see pg. 12.

The pair of outputs A and B are controlled by a one output board. The pair of outputs C and D are controlled by another output board.

Wire as shown below:

 

GND

V+

 

 

 

Stage A

C1

C3

Stage B

C4

C6

 

 

 

Stage C

C7

C9

Stage D

C10

C12

 

 

 

9

Page 9
Image 9
Lochinvar Harmony Output Wiring, WIRING TO 4-20MA MODULATING MOTORS, Wiring To Voltage Modulating Motors, Installation