Stove Installation (for qualified installers only)

Hearth Stove Direct Connection

NOTE:

Direct connections require installation of an airtight, non-combustible block-off plate or damper adapter

NOTE: The chimney must have a clay tile liner. If it does not, the installation must use a positive connection (full reline). The entire fireplace and chimney must be clean, undamaged, and meet all local building codes (UBC, etc.). Damage must be repaired prior to installation. The chimney must be 15' to 33' tall.

Max. 8”

Combustible Mantle

Min. 18"

Floor Protection

(See the section "Floor Protection Requirements" for more details)

Clay

Liner

Stainless steel chimney connector must Extend 1' past the block-off plate or to the flue liner

Airtight

Insulated

Clean-Out

Remove damper or wire it open

Block-off plate or damper adapter

See the section "Stove Placement Requirements" for minimum clearances required.

Figure 14

Interior or Exterior Masonry Chimney

NOTE:

This type of installation requires a UBC approved masonry connector or a factory built (U.L. Listed) wall thimble.

NOTE: The chimney must have a clay tile liner. If it does not, the installation must use a positive connection (full reline). The entire fireplace and chimney must be clean, undamaged, and meet all local building codes (UBC, etc.). Damage must be repaired prior to installation. The chimney must be 15' to 33' tall.

See the section "Stove Placement Requirements" for minimum clearances required.

Chimney connector sections

See the section "Floor Protection Requirements"

Min. 18"

clearance

to ceiling

Clay Liner

This type of installation requires a UBC approved masonry connector or a factory built (U.L. Listed) wall thimble.

Make sure the clean-out seals in place.

Figure 15

© Travis Industries

100-01161

4040608

Page 16
Image 16
Lopi Endeavor owner manual Hearth Stove Direct Connection, Interior or Exterior Masonry Chimney