Lopi Endeavor Floor Protection Requirements, Stove Placement Requirements, Clearances, 100-01161

Models: Endeavor

1 38
Download 38 pages 11.65 Kb
Page 8
Image 8
Floor Protection Requirements

8

Stove Installation (for qualified installers only)

Floor Protection Requirements

Stove must be placed on the Travis Industries legs or Pedestal.

Floor protection must extend 6" to the sides and rear of the stove and 16" to the front of the stove (36" wide by 45-1/2" deep - see Figure 2 and Figure 3). NOTE: when installed with reduced- clearance connector, the clearance to the backwall is less than 6". In this case the floor protection must extend to the wall.

Floor protection must be non-combustible and at least .018" thick (26 guage).

Stove Placement Requirements

Clearances may be reduced by methods specified in NFPA 211, listed wall shields, pipe shields, or other means approved by local building or fire officials.

Stove must be placed so that no combustibles are within, or can swing within (e.g. drapes, doors), 36" of the front of the stove

If the stove is placed in a location where the ceiling height is less than 7', it must follow the requirements in the section "Alcove Installation Requirements"

Must maintain the clearances to combustibles listed below (drywall, furniture, etc.):

Clearances

The following clearances must be met (see Figure 2 and Figure 3)

 

 

 

 

 

 

Minimum Clearance

Singlewall

Reduced

 

 

 

Connector
Clearance*

 

 

 

 

 

 

A

Sidewall to stove

15"

13"

 

B

Backwall to stove

15”

4-1/4"

 

C

Cornerwall to stove

15"

6-1/2"

 

D

Connector to sidewall

24"

21-1/2"

 

E

Connector to backwall

17-3/4"

6-1/2"

 

F

Connector to cornerwall

24"

15"

 

 

 

 

 

*Reduced clearance installations require one of the chimneys and connectors listed below:

AMERI-TEC model DCC with model HS chimney

DURAVENT model DVL with DURATEC or DURA-PLUS chimney

GSW Super Chimney Twenty-One connected directly to appliance

I.C.C. Excel (2100-2 Can.) (103-HT USA) chimney with HP connector

METALFAB model DW connector with TG chimney

OLIVER MACLEOD PROVENT model PV connector with model 3103 chimney

SECURITY model DP connector with SECURITY model ASHT or S2100 chimney

SELKIRK METALBESTOS model DS connector with model SSII chimney

Standard Masonry Chimney with any one of the above listed connectors

NOTE: Reduced clearance connectors may not connect to the flue collar – an appliance adapter may be required.

NOTE: Standard residential installations with reduced clearance connector may use the clearance determined by the manufacturer of the connector for the connector to wall clearance or the clearance listed in this manual. Offsets must be used to maintain the stove to wall clearance.

© Travis Industries

100-01161

4040608

Page 8
Image 8
Lopi Endeavor Floor Protection Requirements, Stove Placement Requirements, Clearances, Travis Industries, 100-01161