Stove Installation (for qualified installers only)

11

Chimney Termination Requirements

Must have an approved cap (to prevent water from entering)

Must not be located where it will become plugged by snow or other material

Must terminate at least 3' above the roof and at least 2' above any portion of the roof within 10' (see Figure 5)

Slanted Roofs

Chimney must extend 3' above the roof

Flat

Chimney must extend 3' above the roof

Chimney must extend 2' above any portion of the roof within 10' of the chimney

Chimney must extend 2' above any portion of the roof within 10' of the chimney

Figure 5

Outside Air Requirements

Required for mobile homes & in certain localities (check with building officials)

Must not be drawn from an enclosed space (garage, unventilated crawl space)

Requires the optional outside air boot (for legs) or pedestal

When using outside air, find a location where the chimney and outside air hole do not interfere with structural members of the home

Pedestal (with insulation) directs air to the stove

Air may be drawn from a ventilated crawl space or use an air duct.

A hole must be cut

 

 

through the floor

Outside

protection and floor

Air Boot

and the rodent

 

 

screen nailed in

 

 

place here (see the

 

 

 

 

optional equipment

 

 

instructions for

 

 

 

 

exact sizes)

 

 

Optional Air Duct (must not be longer than 15' and at least 16 square inches in cross section)

Outside air entrance must be placed so it does not become blocked by snow.

Figure 6

© Travis Industries

100-01161

4040608

Page 11
Image 11
Lopi Endeavor owner manual Chimney Termination Requirements, Outside Air Requirements