Zero-Clearance (Metal) Fireplace Requirements

10

Stove Installation (for qualified installers only)

Zero-Clearance (Metal) Fireplace Requirements

Must utilize a positive (full reline) or direct connection (block-off plate)

Must be manufactured by one of the following manufacturers:

• Marco • Majestic • Heatilator • Preway • Tempco • Superior

Entire fireplace, including chimney, must be clean and undamaged. Any damage must be repaired prior to installation of the insert

Entire fireplace, including chimney, must meet local building requirements

Chimney height: 15' minimum; 33' maximum. Minimum cross section: 28.65 square inches

The damper ("A") and grate ("B") must be removed (see Figure 4). The smoke shelf ("C"), internal baffles ("D"), screen ("E"), and metal or glass doors ("F") may be removed (if applicable). The masonry lining ("G"), insulation ("H"), and any structured rigid frame members (metal sides, floor, door frame, face of the fireplace, etc. – "I") may not be removed or altered

 

 

H

 

F

 

C

A

 

 

 

 

 

 

 

 

D

 

E

 

I

 

 

 

 

 

 

B

 

 

 

G

Figure 4

Drafting Performance

This appliance relies upon natural draft to operate. External forces, such as wind, barometric pressure, topography, or factors of the home (negative pressure from exhaust fans, chimneys, air infiltration, etc.), may adversely affect draft. Travis Industries can not be responsible for external forces leading to less than optimal performance.

Leveling Bolt Installation

Two leveling bolts are included to level the insert if the fireplace has a stepped-up hearth. To install, raise the rear of the insert up and insert the leveling bolts into the holes in the rear corners of the insert. Adjust the bolts until they extend the same height as the hearth steps up. After the insert is installed, fine-tune the leveling bolts to level the insert (see Figure 5).

This distance is the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

hearth step-up. The

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

leveling bolts should

 

 

 

 

 

 

 

 

 

stick out this far from the

 

 

 

 

Fireplace

base of the insert.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Hearth

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The leveling bolts go

into the holes at the

rear corners of the

insert.

Figure 5

© Travis Industries

100-01165

4040806

Page 10
Image 10