Louisville Tin and Stove DVCF653B-R, DVCF654B-R Pilot Adjustment, To Remove Main Burner For

Models: DVCF557B-R DVCF653B-R DVCF654B-R DVCF403B-R DVCF408B-R DVCF558B-R DVCF404B-R DVCF407B-R

1 22
Download 22 pages 34.74 Kb
Page 10
Image 10
PILOT ADJUSTMENT

PILOT ADJUSTMENT

Locate the pilot adjustment screw on the valve. The pilot flame should surround at least the top 3/8” of the powerpile (pilot generator) or flame sensor (see Figure 7). The pilot is unregulated so it will be operating at inlet line pressure (Max. 7” w.c. for Natural Gas and 11” w.c. for Propane). To decrease the pilot flame,

turn the screw clockwise TO REMOVE MAIN BURNER FOR (approximately six full turns to bottom of pilot light channel) until you produce

sufficient flame at the minimum noise level.

PILOT FLAME ADJUSTMENT: Pilot flame should envelop 3/8 to 1/2 inch of the tip of sensor.

3/8” to 1/2”

 

3/8”

 

to

 

 

 

 

1/2”

 

 

 

FIGURE 7A

FIGURE 7B

STANDING PILOT

I.I.D. PILOT

 

 

Pilot Adj. Screw

Pilot Adj. Screw

ROBERTSHAW

ROBERTSHAW

7200ER-SO4

7200IPER-SO4

FIGURE 7C

FIGURE 7D

STANDING PILOT

I.I.D. PILOT

1-1/

2 3/4

FIGURE 8

TO REMOVE MAIN BURNER FOR

INSPECTION AND CLEANING

1.Turn thermostat to lowest setting and allow furnace to cool.

2.Turn off all electric power to furnace.

3.Remove lower grille.

4.Disconnect gas supply to valve.

5.Disconnect wires from gas valve.

6.Remove 15 screws holding burner door to burner box. Pull door forward to remove complete burner, gas valve assembly.

7.After inspecting and cleaning, place burner assembly back into burner box and tighten 15 screws. NOTE: Be sure door gasket is not damaged and will effect a proper seal or pilot outage will occur.

8.Connect wires back to valve.

9.Connect gas supply back to valve.

10.Turn on electric to furnace.

11.Follow lighting instructions, and replace lower grille.

It is recommended that the furnace and all components be inspected at least annually by a qualified service person. This should include the burner, pilot, heat exchanger, and vent system. Be sure that the flow of combustion and ventilation air is not obstructed.

IMPORTANT: Keep burner and control compartment clean. Vacuum control compartment at the start of the heating season and as often as needed.

PROPER BURNER FLAME

The burner flame may be observed by raising the sight glass cover. A proper flame will have a dark blue inner mantle that sits right on top of the burners with a lighter blue outer mantle rising above the burner (See Figure 8). There may be some yellow where the pilot flame and burner flame meet. There is no primary air adjustment on the burner, and proper flame is assured since the correct manifold pressure and orificing has been done at the factory. NOTE: It is advised that the burner flames be checked at least twice during the heating season for any changes in burner flame characteristics. The appliance area must be kept clear and free from combustible materials, gasoline, and other flammable vapors and liquids. This heater comes from the factory with the proper burner orifice for elevations up to 2,000 feet. Heaters installed above 2,000 feet must be derated 4% for every 1,000 feet. For the proper orifice size, find the Model Number and elevation on the

orifice chart. Replace burner orifice.

NATURAL GAS

MODEL 0 to 2,000 - 4,000 - 6,000 - 8,000 –

NUMBER 2,000’ 4,000’ 6,000’ 8,000’ 10,000’

DVCF403B 32 34 35 36 40

DVCF407B 32 34 35 36 40

DVCF557B 3.6m 29 30 30 31

DVCF653B 25 27 28 29 30

ORDER KIT #49840 2287-1 HIGH ALTITUDE KIT

L.P. GAS

MODEL 0 to 2,000 - 4,000 - 6,000 - 8,000 –

NUMBER 2,000’ 4,000’ 6,000’ 8,000’ 10,000’

DVCF404B 49 50 51 52 52

DVCF408B 49 50 51 52 52

DVCF558B 44 45 47 48 49

DVCF654B 2.3mm 44 45 47 48

ORDER KIT #49840 2287-1 HIGH ALTITUDE KIT

Page 10

Page 10
Image 10
Louisville Tin and Stove DVCF653B-R, DVCF654B-R warranty Pilot Adjustment, To Remove Main Burner For, Proper Burner Flame