PROPER OPERATION

PROPER OPERATION

ODS / PILOT FLAME

The pilot pressure has been pre-set at the factory and with proper supply pressure will provide a safe,

reliable ignition source. See Figure 6.

 

 

 

CORRECT

INCORRECT -

INCORRECT - OXYGEN

LOW PRESSURE

LEVEL DROPPING

 

 

 

 

BURNER FLAME

All orificing and pressure setting was done at the factory and, with proper supply pressure, will provide a safe, efficient source of heat. However, if any questions about manifold pressure, have a qualified serviceman check with a manometer, Natural Gas will be 5”, L.P. Gas will be 10” w.c. A proper burner flame (See Figure 7) will produce a reddish-orange flow on the surface of the ceramic burner plaques. If the burner flame has blue streamers or the flame is floating off the surface of the plaques, turn heater off and call a qualified service person. Do not operate heater if all plaques are not glowing. NOTE: There will be approximately ¼” space on the sides and top of the burner that will not glow.

VFM20: When turned to the “LO” setting the two middle plaques will light and glow. When valve is turned to “HI” then

FIGURE 7

CORRECT FLAME

INCORRECT FLAME

all four plaques will be lit.

VFM20 / CORRECT FLAME

“LO”

VFM20 / CORRECT FLAME “HI