GAS CONNECTION

 

GAS CONNECTION

STEP 1.

Make the gas connection between the manual shut off valve and regulator located inside

 

heater cabinet. Hold regulator when tightening connection to prevent damage to regulator

 

and internal tubing. See Figure 5 for completed installation.

NOTE:

All piping and connection must be checked for leaks by the installer. If connections are not

 

exposed, a pressure test must be run. The appliance and its individual shut off valve must

 

be disconnected from the gas supply piping system during any pressure testing at pressures

 

in excess of ½ psig (3.5 kPa). The appliance must be isolated from the gas supply piping

 

system by closing its individual manual shut off valve during any pressure testing of the gas

 

supply piping system at test pressures equal to or less than ½ psig (3.5kPa).