TABLE 1 – first stage pipe sizing |
|
| PROPANE GAS | |||||||||||
10 PSIG Inlet with a 1 PSIG Pressure Drop |
|
|
|
|
|
|
|
|
| |||||
Maximum capacity of pipe or tubing, in thousands of BTU/hr. of L.P. Gas |
|
|
| |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Size of Pipe |
|
|
|
| LENGTH OF PIPE OR TUBING, FEET* |
|
|
| ||||||
Or Copper |
|
|
|
|
|
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
Tubing, Inches | 1 0 | 2 0 | 3 0 |
| 4 0 | 5 0 | 6 0 | 7 0 |
|
| 8 0 | 9 0 | 100 | |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 3/8 | 558 | 383 | 309 |
| 265 | 235 | 213 | 196 |
|
| 182 | 171 | 161 |
Copper | ½ | 1387 | 870 | 700 |
| 599 | 531 | 481 | 443 |
|
| 412 | 386 | 365 |
Tubing | 5/8 | 2360 | 1622 | 1303 |
| 1115 | 988 | 896 | 824 |
|
| 767 | 719 | 679 |
(O.D.) | ¾ | 3993 | 2475 | 2205 |
| 1887 | 1672 | 1515 | 1394 |
| 1297 | 1217 | 1149 | |
| ½ | 3339 | 2295 | 1843 |
| 1577 | 1398 | 1267 | 1165 |
| 1084 | 1017 | 961 | |
Pipe | ¾ | 6982 | 4799 | 3854 |
| 3298 | 2923 | 2649 | 2437 |
| 2267 | 2127 | 2009 | |
Size | 1 | 13153 | 9040 | 7259 |
| 6213 | 5507 | 4989 | 4590 |
| 4270 | 4007 | 3785 | |
| 27004 | 18560 | 14904 | 12756 | 11306 | 10244 | 9424 |
| 8767 | 8226 | 7770 | |||
| 40461 | 27809 | 22331 | 19113 | 16939 | 15348 | 14120 |
| 13136 | 12325 | 11642 | |||
| 2 | 77924 | 53556 | 43008 | 36809 | 32623 | 29559 | 27194 |
| 25299 | 23737 | 22422 | ||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 125 | 150 | 175 |
| 200 | 225 | 250 | 275 |
|
| 300 | 350 | 400 |
| 3/8 | 142 | 130 | 118 |
| 111 | 104 | 9 0 | 8 9 |
|
| 8 9 | 8 2 | 7 6 |
Copper | ½ | 323 | 293 | 269 |
| 251 | 235 | 222 | 211 |
|
| 201 | 185 | 172 |
Tubing | 5/8 | 601 | 546 | 502 |
| 467 | 438 | 414 | 393 |
|
| 375 | 345 | 321 |
(O.D.) | ¾ | 1018 | 923 | 843 |
| 790 | 740 | 700 | 664 |
|
| 634 | 584 | 543 |
| ½ | 852 | 772 | 710 |
| 660 | 619 | 585 | 556 |
|
| 530 | 488 | 454 |
Pipe | ¾ | 1780 | 1613 | 1484 |
| 1381 | 1296 | 1224 | 1162 |
| 1109 | 1020 | 949 | |
Size | 1 | 3354 | 3039 | 2796 |
| 2601 | 2441 | 2305 | 2190 |
| 2089 | 1922 | 1788 | |
| 6887 | 6240 | 5741 |
| 5340 | 5011 | 4733 | 4495 |
| 4289 | 3945 | 3670 | ||
| 10318 | 9349 | 8601 |
| 8002 | 7508 | 7092 | 6735 |
| 6426 | 5911 | 5499 | ||
| 2 | 19871 | 18005 | 16564 | 15410 | 14459 | 13658 | 12971 |
| 12375 | 11385 | 10591 |
*Total length of piping from outlet of first stage regulator to inlet of second stage regulator (or to inlet of second stage regulator furthest away).
Notes: 1) To allow 2 PSIG pressure drop, multiply total gas demand by .707, and use capacities from table.
2)For different first stage pressures, multiply total gas demand by the following factors, and use capacities from table.
First State Pressure PSIG | Multiply by |
|
2 0 | .844 |
|
2 1 | .912 | Data Calculated per NFPA #54 & 58. |
TABLE 4 – Second, Single, or Integral Twin Stage Pipe Sizing
11 Inches Water Column Inlet with a ½ Inch Water Column Drop
Maximum capacity of pipe or tubing in thousands of BTU/hr of | PROPANE GAS | ||||||||||||
Size of Pipe |
|
| LENGTH OF PIPE OR TUBING, FEET* |
|
|
|
| ||||||
Or Copper |
|
|
|
|
|
|
|
|
|
|
|
| |
Tubing, Inches | 1 0 | 2 0 | 3 0 | 4 0 | 5 0 | 6 0 |
| 7 0 | 8 0 | 9 0 | 100 |
| |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 3/8 | 4 9 | 3 4 | 2 7 | 2 3 | 2 0 | 1 9 |
| — | — | — | — |
|
Copper | 1/2 | 110 | 7 6 | 6 1 | 5 2 | 4 6 | 4 2 |
| 3 8 | 3 6 | 3 3 | 3 2 |
|
Tubing | 5/8 | 206 | 141 | 114 | 9 7 | 8 6 | 7 8 |
| 7 1 | 6 7 | 6 2 | 5 9 |
|
(O.D.) | 3/4 | 348 | 239 | 192 | 164 | 146 | 132 |
| 120 | 113 | 105 | 100 |
|
| 7/8 | 536 | 368 | 296 | 253 | 224 | 203 |
| 185 | 174 | 161 | 154 |
|
| 1/2 | 291 | 200 | 161 | 137 | 122 | 110 |
| 102 | 9 4 | 8 7 | 8 4 |
|
Pipe | 3/4 | 608 | 418 | 336 | 287 | 255 | 231 |
| 212 | 198 | 185 | 175 |
|
Size | 1 | 1146 | 788 | 632 | 541 | 480 | 435 |
| 400 | 372 | 349 | 330 |
|
| 2353 | 1617 | 1299 | 1111 | 985 | 892 |
| 821 | 764 | 717 | 677 |
| |
| 3525 | 2423 | 1946 | 1665 | 1476 | 1337 |
| 1230 | 1144 | 1074 | 1014 |
| |
| 2 | 6789 | 4666 | 3747 | 3207 | 2842 | 2575 |
| 2369 | 2204 | 2068 | 1954 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| 125 | 150 | 175 | 200 | 225 | 250 |
| 275 | 300 | 350 | 400 |
|
| 3/8 | — | — | — | — | — | — |
| — | — | — | — |
|
Copper | 1/2 | — | — | — | — | — | — |
| — | — | — | — |
|
Tubing | 5/8 | — | — | — | — | — | — |
| — | — | — | — |
|
(O.D.) | 3/4 | — | — | — | — | — | — |
| — | — | — | — |
|
| 7/8 | — | — | — | — | — | — |
| — | — | — | — |
|
| 1/2 | 7 4 | 6 7 | 6 2 | 5 8 | 5 4 | 5 1 |
| 4 8 | 4 6 | 4 3 | 4 0 |
|
Pipe | 3/4 | 155 | 141 | 129 | 120 | 113 | 107 |
| 101 | 9 7 | 8 9 | 8 3 |
|
Size | 1 | 292 | 265 | 244 | 227 | 213 | 201 |
| 191 | 182 | 167 | 156 |
|
| 600 | 544 | 500 | 465 | 437 | 412 |
| 392 | 374 | 344 | 320 |
| |
| 899 | 815 | 749 | 697 | 654 | 618 |
| 587 | 560 | 515 | 479 |
| |
| 2 | 1731 | 1569 | 1443 | 1343 | 1260 | 1190 |
| 1130 | 1078 | 992 | 923 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
*Total length of piping from outlet of regulator to appliance furthest away. |
| Data Calculated per NFPA #54 & 58. |
Page 8