Trouble Shooting Two

Trouble Shooting Two

PROBLEM

POSSIBLE CAUSE

CORRECTION

Moisture collects on

Hot and humid conditions.

Extremely hot and humid conditions can cause

outside surface of cabinet.

 

condensation on the outside of unit. As

 

 

humidity and/or temperature decreases,

 

 

condensation will disappear.

Moisture collects on inside

Too many door openings.

Limit the amount of door openings.

of the unit.

Prolonged door openings.

Limit the amount of time with the door open.

 

Hot and humid conditions.

Extreme hot and humid conditions. Move unit

 

 

to a controlled environment. May consider

 

 

having the defrost section changed from 12 to

 

 

6 hours.

 

Defrost thermistor out of specification.

Consult dealer or servicer for diagnosis.

The unit is too warm or too

Adjustment of the temperature control

Adjust the temperature control to warmer or

cold.

knob.

colder setting and allow 24 hours before

 

 

readjusting if necessary.

 

Temperature control slide in the

Adjust temperature control slide as necessary

 

refrigerator section too far open.

in the refrigerator section of the unit.

The unit is warm inside

Drip tray heater is on.

The drip tray heater will remain energized with

with the temperature

 

the control knob in the off position. Unplug the

control know in the “OFF”

 

unit if storing or leaving the unit off for

position.

 

extended periods of time.

Items on door shelf

The upper two shelves of the door can

Turn the temperature control knob to a lower

sometimes freeze.

freeze under warm conditions.

number or move the commodities to the

 

 

refrigerator section.

Diagnostic LED

In the back in the grille there is a diagnostic/status LED. This led is used to help diagnosis any problems with the unit and to tell its status.

LED status

Code/Problem

Not on or blinking

Unit does not have power

steadily blinking once per second

Unit temperature control is in the "OFF" position

Continuously on

Unit is "ON" and operating correctly

2 blinks and pause; repeated pattern

Defrost thermistor out of range

3 blinks and pause; repeated pattern

Evaporator normal cycling thermistor out of range

4 blinks and pause; repeated pattern

Control potentiometer out of range

2 blinks, pause, 3 blinks, pause; repeated pattern

Both defrost and evaporator thermistor are out of range

 

 

8

Page 9
Image 9