Trouble Shooting Two
PROBLEM | POSSIBLE CAUSE | CORRECTION |
Moisture collects on | Hot and humid conditions. | Extremely hot and humid conditions can cause |
outside surface of cabinet. |
| condensation on the outside of unit. As |
|
| humidity and/or temperature decreases, |
|
| condensation will disappear. |
Moisture collects on inside | Too many door openings. | Limit the amount of door openings. |
of the unit. | Prolonged door openings. | Limit the amount of time with the door open. |
| Hot and humid conditions. | Extreme hot and humid conditions. Move unit |
|
| to a controlled environment. May consider |
|
| having the defrost section changed from 12 to |
|
| 6 hours. |
| Defrost thermistor out of specification. | Consult dealer or servicer for diagnosis. |
The unit is too warm or too | Adjustment of the temperature control | Adjust the temperature control to warmer or |
cold. | knob. | colder setting and allow 24 hours before |
|
| readjusting if necessary. |
| Temperature control slide in the | Adjust temperature control slide as necessary |
| refrigerator section too far open. | in the refrigerator section of the unit. |
The unit is warm inside | Drip tray heater is on. | The drip tray heater will remain energized with |
with the temperature |
| the control knob in the off position. Unplug the |
control know in the “OFF” |
| unit if storing or leaving the unit off for |
position. |
| extended periods of time. |
Items on door shelf | The upper two shelves of the door can | Turn the temperature control knob to a lower |
sometimes freeze. | freeze under warm conditions. | number or move the commodities to the |
|
| refrigerator section. |
Diagnostic LED
In the back in the grille there is a diagnostic/status LED. This led is used to help diagnosis any problems with the unit and to tell its status.
LED status | Code/Problem |
Not on or blinking | Unit does not have power |
steadily blinking once per second | Unit temperature control is in the "OFF" position |
Continuously on | Unit is "ON" and operating correctly |
2 blinks and pause; repeated pattern | Defrost thermistor out of range |
3 blinks and pause; repeated pattern | Evaporator normal cycling thermistor out of range |
4 blinks and pause; repeated pattern | Control potentiometer out of range |
2 blinks, pause, 3 blinks, pause; repeated pattern | Both defrost and evaporator thermistor are out of range |
|
|
8