Maytag HR650DJLS manual Temperature-PressureRelief Valve, Instructions for Installation cont’d

Models: HR630SJRT HR640SJLS HR640DJLS HR630DJRT HR650DJRS HR630SJLS HR6120SJRT HR630DJLS HR650SJRS HR650DJLS HR640DJRT HR650SJLS HR640DJRS HR640SJRT HR640SJRS HR6120DJRT HR682DJRT HR666SJRT HR652DJRT HR666DJRT HR682SJRT HR652SJRT

1 36
Download 36 pages 53.46 Kb
Page 12
Image 12
Temperature-Pressure Relief Valve

Instructions for Installation (cont’d)

Temperature-Pressure Relief Valve

Manual backgroundWARNING

At the time of manufacture this water heater was provided with a combination temperature-pressures relief valve certified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials, as meeting the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, and the current edition of ANSI Z21.22 • CSA 4.4 and the code requirements of ASME. If replaced, the valve must meet the requirements of local codes, but not less than a combination temperature and pressure relief valve certified as meeting the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22 • CSA 4.4 by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials.

The valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 lbs./sq. in.) and a discharge capacity not less than the water heater input rate as shown on the model rating plate. (Electric heaters - watts divided by 1000 x 3412 equal BTU/Hr. rate.)

Your local jurisdictional authority, while mandating the use of a temperature-pressure relief valve complying with ANSI Z21.22 • CSA 4.4 and ASME, may require a valve model different from the one furnished with the water heater.

Compliance with such local requirements must be satisfied by the installer or end user of the water heater with a locally prescribed temperature-pressure relief valve installed in the designated opening in the water heater in place of the factory furnished valve.

For safe operation of the water heater, the relief valve must not be removed from it’s designated opening or plugged.

The temperature-pressure relief valve must be installed directly into the fitting of the water heater designated for the relief valve. Position the valve downward and provide tubing so that any discharge will exit only within 6 inches above, or at any distance below the structural floor. Be certain that no contact is made with any live electrical part. The discharge opening must not be blocked or reduced in size under any circumstances. Excessive length, over 30 feet, or use of more than four elbows can cause restriction and reduce the discharge capacity of the valve.

No valve or other obstruction is to be placed between the relief valve and the tank. Do not connect tubing directly to discharge drain unless a 6” air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.

The Discharge Pipe:

Must not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restrictions.

Must not be plugged or blocked.

Must be of material listed for hot water distribution.

Must be installed so as to allow complete drainage of both the temperature-pressure relief valve, and the discharge pipe.

Must terminate at an adequate drain.

Must not have any valve between the relief valve and tank.

Manual backgroundWARNING

The temperature-pressure relief valve must be manually operated at least once a year. Caution should be taken to ensure that (1) no one is in front of or around the outlet of the temperature-pressure relief valve discharge line, and (2) the water manually discharged will not cause any bodily injury or property damage because the water may be extremely hot.

If after manually operating the valve, it fails to completely reset and continues to release water, immediately close the cold water inlet to the water heater, follow the draining instructions, and replace the temperature-pressure relief valve with a new one.

HOTCOLD

HOT COLD

CONDUITManual background

TEMPERATURE-

PRESSURE RELIEF VALVE

Manual background DISCHARGE PIPE (Do not cap or plug)

6” AIR GAP

FLOOR DRAIN

12

Page 12
Image 12
Maytag HR650DJLS, HR652SJRT, HR682SJRT, HR666DJRT Temperature-PressureRelief Valve, Instructions for Installation cont’d