SECTION 2 - INSTALLATION

A.Gas Utility Rough-In Recommendations

The following gas system specifications are STRONGLY RECOMMENDED. Deviating from these recommendations may affect the baking performance of the oven.

Gas Meter

One or two oven cavities: 354 l/sec meter

Three or four oven cavities: 566 l/sec meter

Gas Line

DEDICATED LINE from the gas meter to the oven

50.8mm pipe for natural gas

38.1mm pipe for propane

Maximum length: 61m. Each 90° elbow equals 2.13m of pipe.

B.Connection

WARNING

Some procedures in this section may require conver- sions, readjustments, or service on the oven's gas system. Before performing these procedures, check that the main gas supply valve and the circuit breaker/fused disconnect are in the OFF ("O") position. After completing these proce- dures, perform a gas leak test before operating the oven.

CAUTION

The terms of the oven's warranty require all start-ups, conver- sions and service work to be performed by a Middleby Marshall Authorized Service Agent. The installation, start-up and changes required when changing from one gas type to another can be performed ONLY by a certified professional.

NOTE: The gas supply connection should be according to applicable ISO 228-1 or ISO 7-1 recommendations. All aspects of the gas supply connection must comply with current IEC/CEE requirements and with all applicable local, national, and inter- national codes.

Check the oven’s gas supply requirements before making the gas utility connection. Gas supply requirements are listed on the oven’s serial plate.

Check the serial plate to determine the type of gas to be used with the oven. Check that the gas type indicated matches the local supply at the installation. If the gas type on the serial plate does NOT match the local supply, directions for converting the oven for use with other gases are described in Preparation for Use with Various Gases, in this section.

Refer to the instructions in the gas hose package (included in the Installation Kit) before connecting the gas line. One gas line connection method is shown in Figure 2-15; however, compliance with the applicable standards and regulations is mandatory.

Figure 2-15 - Flexible Gas Hose Installation

To Gas

Supply Pipe

Appliance

Connection/Male

Nipple

90°

Full-Flow Gas

Elbow

Shutoff Valve

Flexible

Gas Hose

Figure 2-16 - Gas Burner and Piping Assembly

Supply (inlet)

Orifice

pressure tap

(manifold)

Multifunction Gas Valve

pressure tap

Burner Blower

High Flame

Solenoid Valve

Governor

 

disabled for

 

liquid

 

propane (LP)

 

operation

 

Governor

Multifunction

enabled for

Gas Valve

natural gas

 

operation

 

Gas Burner

Pilot Line

Low Flame

Bypass Line

Union

Pilot pressure tap

12

Page 12
Image 12
Middleby Marshall PS360-U installation manual Gas Utility Rough-In Recommendations, Gas Meter, Gas Line