Step 10. BURNER ADJUSTMENTS

Note - The air shutter for the burner primary air opening is factory-set. Do not adjust the factory- set position. The factory-set position is shown in

Figure 25.

*Air Shutter

BurnerOpening

Venturi

Tube

Orifice

Millivolt Shown

*Note - Do Not Adjust the Factory-Set Position. The shutter opening is shown in the table below.

MAIN BURNERFACTORY SHUTTER SETTING
Manually-Reset Safety Limit Switch

This appliance is equipped with a manually-reset blocked flue safety limit switch. Refer to Figure 26 for its location. If, during appliance operation, the flame goes out (independently of the burner on/ off wall switch), it may be due to the operation of this safety limit switch. First allow the appliance to cool, then reset the safety switch by pushing the red reset button on the back of the switch.

To access the blocked flue safety limit switch refer to Figure 26:

A- To access the blocked flue safety switch when top radiant panel is not covered with non- combustible material:

1- Lift up and remove top radiant panel/eyebrow assembly on the control side of unit.

2- Reach between the cabinet side and the firebox side wall and locate the blocked flue safety switch.

3- Push the red reset button on the switch.

The applilance should then relight and remain lit. If this does not occur, turn off the appliance and call a qualified service technician.

B- To access the blocked flue safety switch when top radiant panel is covered with non- combustible material:

NOTE - This procedure should only be performed by a qualified service technician.

Important - Turn electrical power off before beginning this procedure.

Natural Gas

Propane

1 - Lower bottom hinged panel on the control side of the fireplace. Remove the modesty panel

Models inches

Gas

and glass enclosure panel as described on page 5, Steps 3, 4, 5 and 6 under "Detailed Installation

inches

Steps" heading.

(mm)

EBVST

(mm)

2 - Remove the side baffle securing screws (5) and then remove the baffle.

3 - Remove the safety switch bracket securing screws (2), and pull the switch/bracket assembly

through the side panel slot.

EBVPF

1/16 (1.5) 7/16 (11)

EBVCR

EBVCL

Figure 25

Step 11. Spillage Test and Safety Limit Switch OperationSpillage Test

After appliance installation, perform this spillage test to verify that proper venting conditions exist:

4

- Push the red reset button on the switch.

5

- Reinstall the switch/bracket assembly.

6

- Reinstall the side baffle.

7

- Reinstall front glass door.

8

- Raise the bottom hinged panel.

The appliance should then relight and remain lit. If this does not occur, check unit for a blocked flue condition.

SAFETY SWITCH LOCATION (EBVCL SHOWN) EBVST and EBVPF Safety Switch Location Also as Shown;

EBVCR Location on the Left End of the Fireplace.

1- Place unit in its normally-operated con- dition, that is, with the glass enclosure pan- els in place.

2 - Close all doors and windows in the room. Turn on all exhaust fans in the house. 3 - Light the appliance.

4 - Wait 15 minutes.

5 - To check for venting action, start by holding a smoke producing device within an inch of one edge (side edge, not top or bottom edge) of one glass enclosure panel. The smoke should be drawn toward the edge of the glass enclosure panel. Continue the test by moving the smoke producing device along the entire length of both side-edges of the glass door. Repeat the test for all glass enclosure panels.

6 - If the smoke is not drawn towards the edges of the glass door turn off the appli- ance and call a qualified service technican.

FIREBOX

SIDE WALL

BRACKET

SECURING SCREW

SAFETY SWITCH

Figure 26

FIREBOX SIDE BAFFLE SECURING SCREW

FIREBOX SIDE BAFFLE

MANUALLY-RESET

SAFETY LIMIT SWITCH

TOP RADIANT PANEL

AND EYEBROW

CABINET

SIDE WALL

14

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.