All Models

Step 8. (Refer to Figure 29 )

A.Remove the orifice from the manifold and replace it with the one provided in the kit. See the following table for orifice sizes for natural and propane models. Figure 34 illustrates the orifice.

B.Install the burners as shown in Figure 29. The primary air opening can be adjusted by removing the venturi tube air shutter securing screw and placing it in the other hole provided nearby. The correct hole usage for this screw for the gas being used can be determined by the air shutter gap indicated in Figure 25 on page 14.

Model

Orifice size

Elevation

Feet

No.

 

 

Nat.

Prop.

(meters)

 

 

 

 

 

EBVST

#32

#50

 

EBVPF

0-4500

 

 

EBVCR

#34

#50

(0-1372)

EBVCL

 

 

 

 

 

 

 

 

Figure 34

18

Kit Catalog No.H2199 and H2201

THIS APPLIANCE HAS BEEN CONVERTED TO:

NATURAL GAS

INPUT BTU/HR – 37,500 MANIFOLD PRESSURE – 3.5" ORIFICE SIZE – #32

Kit Catalog No.

H2203 and H2205

THIS APPLIANCE HAS BEEN CONVERTED TO:

NATURAL GAS

INPUT BTU/HR – 34,000 MANIFOLD PRESSURE – 3.5" ORIFICE SIZE – #34

Kit Catalog No.

H2198 and H2200

THIS APPLIANCE HAS BEEN CONVERTED TO:

PROPANE/LPG

INPUT BTU/HR – 34,000 MANIFOLD PRESSURE – 10.0" ORIFICE SIZE – #50

Figure 35

NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.

Step 9. Reassemble the remaining components by reversing the procedures outlined in the preceding steps. Use pipe joint compound or Teflon tape on all pipe fittings before installing (ensure propane resistant compounds are used in propane applications, do not use pipe joint compounds on flare fittings).

Step 10. Attach the conversion label provided in the conversion kit to the rating plate on the appliance. Figure 35 shows all of the labels for all of the kits covered by this manual as shown in the tables on page 17. Compare the label provided in the kit being installed to the appropriate label shown in Figure 35.

Step 11. Turn on the gas supply and test for leaks as shown in step 5 on page 11.