Symptom

Possible Cause

What To Do

 

 

 

 

 

 

 

UPS will not turn on

On/Off/Test button not

Press and release the On/Off/

 

 

 

pushed

Test button to start UPS

 

 

UPS operates in

Input AC circuit breaker is

Reset circuit breaker by

 

 

battery mode only,

tripped

pressing the plunger back in.

 

 

even though there

 

If the AC circuit breaker trips

 

 

is normal AC

 

after UPS starts up, reduce

 

 

present

 

the load on the UPS

 

 

Fault LED is

UPS has detected an

Call for service

 

 

illuminated

internal fault

 

 

 

Site Wiring Fault

Incorrect service wiring

Have a Qualified Electrician

 

 

LED is illuminated

 

correct the service wiring

 

 

The AC normal

The UPS is being

Disconnect the computer

 

 

LED is illuminated,

controlled via its

cable from the UPS and press

 

 

but there is no out-

communications port

the On button. If UPS works

 

 

put

 

normally, the software has

 

 

 

 

control of the UPS

 

 

UPS does not

The batteries may be weak

Charge the batteries for 8-

 

 

provide expected

or at the end of useful

hours and retest. If the runtime

 

 

runtime

service life

is still less than expected, the

 

 

 

 

batteries may need to be

 

 

 

 

replaced, even though the

 

 

 

 

Weak/Bad Battery LED is not

 

 

 

 

illuminated

 

 

Weak/Bad Battery

Loose connections at the

Check battery connections,

 

 

LED is illuminated

batteries, Weak batteries,

charge the batteries for 8-

 

 

 

Bad batteries

hours, replace the batteries

 

 

 

 

 

 

 

UPS occasionally

Normal operation

The UPS is performing its

 

 

emits a beep

 

intended function

 

 

 

 

 

 

 

Overload LED is

The load has exceeded the

Check the specifications (see

 

 

illuminated and a

UPS's capacity

section 8). Remove part of

 

 

constant alarm

 

the load

 

 

The Boost LED or

The UPS is in either the

The UPS is performing its

 

 

Buck LED is blink-

Boost mode or the Buck

intended function

 

 

ing.

mode

 