BATTERY SYSTEM

English

BATTERY SYSTEM

Battery Type

Sealed, Non-Spillable, Maintenance Free, Value Regulated Lead Acid

 

 

 

 

 

Typical Recharge Time

 

8-hours from total discharge

 

 

 

 

 

 

 

Typical Battery Life

3-5 years, depending on discharge cycles and ambient temp

 

 

 

 

 

 

System Voltage

36VDC

36VDC

36VDC

72VDC

72VDC

 

 

 

 

 

 

Battery: Quantity/Rating

3-12V7.2Ah

3-12V7.2Ah

3-12V8.5Ah

6-12V7.2Ah

6-12V8.5Ah

 

 

 

 

 

 

Runtime: Half Load (minutes)

17

15

11

13

8

 

 

 

 

 

 

Runtime: Full Load (minutes)

8

5

4

5

3

 

 

 

 

 

 

SURGE PROTECTION AND FILTERING

Surge Energy Rating

800 J (600 J)

 

 

 

 

 

Surge Current Capability

6500 Amps total

 

 

 

 

Surge Response Time

0 ns (instantaneous) normal mode; <5 ns common mode

 

 

 

 

Surge voltage let-through (as

<5%

 

 

a percentage of an applied

 

 

ANSI C62.41 Cat. A +/-6 kV)

 

 

 

 

 

 

 

10/100 Base-T surge protec-

 

 

 

tion let-through (as a percent-

<5%

 

 

age of an applied +/-6 kV 1.2/

 

 

 

50 us, 500 a 8/20 uS test)

 

 

 

 

 

 

 

Telephone line surge protec-

 

 

 

tion let-through (as a percent-

<1%

 

 

age of an applied +/-6 kV 1.2/

 

 

 

50 us, 500a 8/20 uS test)

 

 

 

 

 

 

Noise Filter

normal and common mode EMI/RFI suppression

 

 

 

 

Audible Noise at 1 m (3 ft.)

<45 dBA

 

<60 dBA

 

 

 

 

 

 

ENVIRONMENTAL

 

 

Operating Temperature (max)

0 to 40°C (+32 to +104°F)

 

 

 

 

 

Storage Temperature

-15 to +45°C (+5 to +113°F)

 

 

 

 

 

Operating/Storage Humidity

95% Non-Condensing

 

 

 

 

 

Operating Elevation

0 to 3,000m (0 to +10,000 ft)

 

Storage Elevation

0 to 15,000m (0 to +50,000 ft)

 

 

 

 

 

 

PHYSICAL

 

 

 

 

 

 

Size - Net

17.0 x 17.3 x 3.5"

24.0 x 17.3 x 3.5"

 

D X W X H

432 x 440 x 89 mm

610 x 440 x 89 mm

 

Weight - Net

46.2 lbs

110.9 lbs

 

21.0 Kgs

50.4 Kgs

 

 

 

 

 

 

 

Size - Shipping

23.6 x 20.0 x 9.0"

39.4 x 23.6 x 9.0"

 

D X W X H

600 x 508 x 230 mm

1000 x 600 x 230 mm

 

 

 

 

 

Weight - Shipping

55.0 lbs

127.0 lbs

 

25.0 Kgs

57.3 Kgs

 

 

 

 

 

 

 

REGULATORY COMPLIANCE

 

 

 

 

 

 

Safety and Approvals

UL1778, cUL (CSA 22.2 no. 107.1)

 

 

 

 

 

EMC Verification

FCC Class B, CE certified

 

 

 

 