NOTE: The MCP 5000iE and 7000iE's AC input must be connected to an AC circut breaker which will provide for an emergency power off. (Must be performed by Authorized

Service Personnel ONLY)

Model

MCP 5000iE

MCP7000iE

Input Circuit Breaker

40 Amp

50 Amp

Input Wire Size/Temp

8 AWG/min75°C

6 AWG/min75°C

Wire Conductor

Three conductor, copper wire only

Tightening torque for

Torque 17.6Lbs (8kg)

pressure wire connectors

having screws

 

 

Block diagram of the MCP 5000iE and MCP 7000iE input and output wiring.