![](/images/new-backgrounds/1121429/12142919x1.webp)
NOTE: The MCP 5000iE and 7000iE's AC input must be connected to an AC circut breaker which will provide for an emergency power off. (Must be performed by Authorized
Service Personnel ONLY)
Model | MCP 5000iE | MCP7000iE |
Input Circuit Breaker | 40 Amp | 50 Amp |
Input Wire Size/Temp | 8 AWG/min75°C | 6 AWG/min75°C |
Wire Conductor | Three conductor, copper wire only | |
Tightening torque for | Torque 17.6Lbs (8kg) | |
pressure wire connectors | ||
having screws |
|
|
Block diagram of the MCP 5000iE and MCP 7000iE input and output wiring.
English
9