CONFIGURABLE PARAMETERS AND SETTINGS

English

CONFIGURABLE PARAMETERS AND SETTINGS

(These items may require optional software or hardware)

FUNCTION

FACTORY DEFAULT

USER CHOICES

DESCRIPTION

UPS ID

MCP-E SERIES

Up to 64 characters to

Use this function to uniquely identify the

 

 

define the UPS

UPS in your network configuration

 

 

 

 

Battery installation date

Date of Manufacture

Date of Battery Replacement-

Enter the current date when

 

 

day/month/year (xx/xx/xxxx)

replacing the batteries

 

 

 

 

Battery life in days

Preset for 1826 days

Enter up to 5 characters

When replacing the batteries,

 

 

 

calculate the actual number of days in

 

 

 

use after manufacture date and then

 

 

 

enter this expected life for your

 

 

 

environment

 

 

 

 

Auto Restart:

Enabled

User may Enable or

When "enabled", the UPS will

Enable/Disable

 

Disable Autorestart

automatically restart and operate in

 

 

 

normal AC mode after a low battery

 

 

 

shutdown and normal AC has returned

 

 

 

 

Set audible

Enabled

User may Enable or Disable

Enabled: The UPS will emit an

alarm state

 

until Low Battery Warning

audible alarm every 10 seconds

 

 

 

when in the battery mode.

 

 

 

Disabled until Low Battery Warning:

 

 

 

Used when software is controlling the

 

 

 

UPS or to silence the alarm. In

 

 

 

this state, the UPS will not emit

 

 

 

an audible alarm until the unit

 

 

 

reaches low battery warning level.

 

 

 

 

Enable or Disable all

Disabled

User is required to enable prior

This is a safety feature to prevent

UPS functions

 

to operation. The UPS will not

operation while packaged during

 

 

operate until enabled.

shipping.

 

 

 

 

Set Inverter Output

120 vac on 120 volt units.

120 volt units: 100,110,115,120

Allows the customer to set the voltage

Voltage

230 vac on 230 volt units.

230 volt units: 220,230,240

based on the environment in which the

 

 

 

unit will be installed. This voltage is

 

 

 

set via external dip switch. The dip

 

 

 

switch is on the rear panel of the unit.

 

 

 

 

26