SNMP-NV6
Page 9
9. Select the SNMP-NV6 card in the Device List and then click on the Modify button.
Enter the account and password. The default account and password are admin
and password respectively.
10. Click on the Configuration button and then configure the essential network
parameters.
4.2 Configure the SNMP-NV6 card through COM Port
1. Prepare a workstation (Microsoft Windows 2000, 2003, 2008, XP, Vista, Win7 or
later).
2. Use the RJ45 to DB9 serial cable (provided) to connect the SNMP-NV6 card’s COM
port with the workstation’s COM port.
3. Set both of the dipswitches of the SNMP-NV6 card to OFF position (normal mode)
to enable the network transmission.
4. From the workstation running Windows 2000, 2003, 2008, or XP, open
HyperTerminal in the Accessories Program Group. From the workstation running
Windows Vista or 7, download the Putty software from the Internet to execute the
configuration.
5. Configure the COM port’s parameters: 2400 bps, 8 data bits, no parity, 1 stop bit
and no flow control.