4.8 Setting functional list

The list of the setting functions of BACnet IF is arranged below.

Chapter 8 explains the usage of each function.

Setting information tak es backup. For the backup pr ocedure, refer to Appendix 3.

Item Details
G-50A Tab G-50A and the air-conditionin g unit for management are set up. (*1)
G-50A setup The information on G-50A for management is set up.
G-50A number, IP address, Port number (80 fixation : for LAN c ommunication of G-50A).
Group setup The information on t he group registered into G-50A is set up.
Grou p number, Apparatus attribute, Out Of Service
BACnet Tab It sets up about BACnet communication.
Broadcast IP-Address The IP address of a building management system is set up.
Timeserver IP-Address The IP address of time synchronous origin is set up.
BACnet Appl ication setup The communication parameter of BACnet is set up. Port numbe r (47808 fixation: for BACnet
communication), Venders ID (99 fixation), DeviceID APDU timeout, Number of times of APDU retries,
Check command (I-AM) transmitting int erval
Notification function is set up.
COV Notification COV number, IP address, Notification type
EVENT Notification Processes ID, NClassID, Priority, IP address, Notification type
Event Notification setup
Conditions of Notification COV Notification: COV number, Change increment setup
EVENT Notification : NClassIDEvent-EnableLimit-Enable
Notification type, Time_Delay
System Tab The function of a system is set up.
Unit of Temperature The unit (Fahrenheit, Celsius) of the tempe rature data used by BACnet is switched.
Drive Mode Type Use in operation m ode "DRY" is set up.
Air Speed Type Use of wind velocity "Mid2, Mid1" is s et up.
Time Set The notification to G-50 A of a time synchronous notification is set up. (*2)
Auto Reboot The execution time of automati c reboot is set up.
File menu Execut ion of file operation and an end of a tool.
New Settings An untit led setting file is newly creat ed.
Open Settings System inform ation is loaded from the saved fil e.
Save Settings System setting information is saved at a f ile (overwrite).
Save Settings As... System setting information is saved at a file.
Exports System setting information is outputted to a CSV file.
Properties The IP address of the personal computer, which is setting up BACnetIF, is set up.
[127.0.0.1] is set up when BACnetIF is set up in the same personal computer as a setting tool.
Exit A setting tool is ended.
BACnetIF menu The contents of a system setting are transmitted between Set BACnet (setting tool) and BACnetIF.
Get Settings System sett ing information is transmitted t o BACnetIF.
Put Settings System setting information is read f rom BACnetIF.
*1 Since the information on the set-up a ir-conditioning unit is not regis tered into G-50A, it is necessary to s et it up on G-50A separately.
*2 Setup of "Timeserver IP-Address" is requi red for use of this function.