Object Object
type
Instance
number *5)
Management item Test procedure Result
Prohibition of local
operation (Mode)
BV xxxx14 Inactive: Pe rmit
Active: Prohibit
- Change remote control hand operation (Mode) of
a group from BMS.
Then, it checks by G-50A whether the state of an
air-conditioning system is equal t o the state where it
was operated by BMS.
- Change remote control hand operation (Mode) of
a specific group by G-50A.
Then, the state of BAC net IF is read from BMS
and it checks in the same state as G-50A.
Prohibition of local
operation (filter reset)
BV xxxx15 Inactive: Pe rmit
Active: Prohibit
- Change remote control hand operation (filter
reset) of a specific group by G-50A.
Then, the state of BAC net IF is read from BMS
and it checks in the same state as G-50A.
Prohibition of local
operation (Set Temp.)
BV xxxx16 Inactive: Pe rmit
Active: Prohibit
- Change remote control hand operatio n (Set
Temp) of a group from BMS.
Then, it checks by G-50A whether the state of an
air-conditioning system is equal t o the state where it
was operated by BMS.
- Change remote control hand operatio n (Set
Temp) of a specific group by G-50A.
Then, the state of BAC net IF is read from BMS
and it checks in the same state as G-50A.
Communication State BI xxxx20 Inactive: Normal
Active: Abnormal
- Remove the transmission line of LAN c onnected
to G-50A.
Then, a state is read from BMS and it checks in
Abnormalities (ACTIVE).
- Connect the transmission line of LAN t o G-50A.
Then, the state of BAC net IF is read from BMS
and it checks in Normal (INACTIVE).
- Remove the transmission line of LAN c onnected
to G-50A.
Then, it checks whether Event Notification is
transmitted to BMS from PAC-YG31CDA.
System Forced Off BV xx9921 Inactive: Released
Active: Effective
- Change the system forced Off of a group from
BMS.
Then, it checks by G-50A whether the state of an
air-conditioning machine is equal to the s tate where
it was operated by BMS.
Air direction
(setup)
MO xxxx22 01: Horizontal
02: Down 60%
03: Down 80%
04: Down100%
05: Swing
- Change the wind direction of a group f rom BMS.
Then, it checks by G-50A whether the state of an
air-conditioning machine is equal to the s tate where
it was operated by BMS.
Air direction
(state)
MI xxxx23 01: Horizontal
02: Down 60%
03: Down 80%
04: Down100%
05: Swing
- Change the wind direction of a group b y G-50A.
Then, the state of BAC net IF is read from BMS
and it checks in the same state as G-50A.
*1) It can use, if dry operation use is set up.
*2) It can use, if use of Mid1/Mid2 is set up.
*3) The group of LC serves as an item with an invalid attribute.
*4) As for the operation mode of the group of LC, an attribute serves as ventilation fixation.
*5) XXXX of an instance number consists of G50 number + group numbers.
*6) BMS:Building Management System
39