BACnet Interface PAC-YG31CDA Site Adjustment sheet

G-50A Number [ ] IPaddress[ . . . ] Group Number[ ]

Object Object
type
Instance
number *5)
Management item Test procedure Result
On/Off (setup) BO xxxx01 Inactive: On
Active: Off
- Change operation/stop of a certai n group from
BMS *6.
Then, it checks by G-50A whether the state of an
air-conditioning system is equal t o the state where it
was operated by BMS.
On/Off (state) BI xxxx02 Inactive: On
Active: Off
- Change operation/stop of a group by G-50A.
Then, the state of BACnet I F is read from BMS
and it checks in the same state as G-50A.
Alarm signal BI xxxx03 Inactive: Normal
Active: Abnormalities
- Make a malfunction of unit.
Then, a state is read from BMS and it checks in
Abnormalities (ACTIVE).
- Restore a malfunction of unit.
Then, the state of BAC net IF is read from BMS
and it checks in Normal (INACTIVE).
Then, it checks whether Event Notification is
transmitted to BMS from BACnet IF.
Error Code MI xxxx04 01: Normal
02: Other abnormality
03: Refrigerant system abnormality
04: Water system abnormality
05: Air system abno rmality
06: Electric system abnormality
07: Sensor abnormality
08: Communication abnormality
09: System abnormality
- Remove the transmission line of M-NET
connected to G-50A.
Then, the state of BAC net IF is read from BMS
and it checks in the Communication abnormality
(08).
- Connect the transmission line of M-NET to G-
50A.
Then, that of a BAC net IF state is read fromBMS,
and it checks in Normal (01).
Operation mode
(setup)
MO xxxx05 01: Cool
02: Heat
03: Fan
04: Auto
05: Dry *1)
- Change the operation mode of a group fr om
BMS.
Then, it checks by G-50A whether the state of an
air-conditioning system is equal t o the state where it
was operated by BMS.
Operation mode
(state)
MI xxxx06 01: Cool
02: Heat
03: Fan
05: Dry *1)
- Change the operation mode of a group by G- 50A.
Then, the state of BAC net IF is read from BMS
and it checks in the same state as G-50A.
Fan Speed
(setup)
MO xxxx07 01: Lo
02: Hi
03: Mid2 *2)
04: Mid1 *2)
- Change the Fan Speed of a group from BMS.
Then, it checks by G-50A whether the state of an
air-conditioning system is equal t o the state where it
was operated by BMS.
Fan Speed
(state)
MI xxxx08 01: Lo
02: Hi
03: Mid2 *2)
04: Mid1 *2)
- Change the Fan Speed of a group by G-50A.
Then, the state of BAC net IF is read from BMS
and it checks in the same state as G-50A.
Room Temp. AI xxxx09 °F / °C - R ead the Room Temp of a group from BMS and
check whether it is the same as the state of G-50A.
Set Temp. AV xxxx10 °F / °C - Read the i ndoor setting temperature of a group
from BMS, and check whether it is the same as t he
state of G-50A.
Filter Signal BI xxxx11 Inactive: OFF
Active: ON
- Read the Filter Signal of a group from BMS, an d
check whether it is the same as the state of G-50A.
Filter Signal Reset BV xxxx12 Inactive: RESET
ACTIVE: Void
- Set a Filter Signal to RESET (INACTIVE) from
BMS to the group, which has detected the Filter
Signal.
Then, the state of an air-conditioning syst em is
equal to the state where it was oper ated by BMS,
or it checks by G-50A.
Prohibition of local
operation (On/Off)
BV xxxx13 Inactive: Pe rmit
Active: Prohibit
- Change remote control hand operation (On/Off) of
a group from BMS.
Then, it checks by G-50A whether the state of an
air-conditioning system is equal t o the state where it
was operated by BMS.
- Change remote control hand operation (On/Off) of
a specific group by G-50A.
Then, the state of BAC net IF is read from BMS
and it checks in the same state as G-50A.

38