8Initial Settings
After completing the procedures described in "6. Installation" and "7. Wiring Instructions", set the initial settings in accordance with the procedure described below.
(1)
10s1s
SW06SW07
Note:
•An address from 01 to 50 can be set.
•Set an address that is not the same as that of another unit.
The address is set to "01" at factory default.
In the case of address "41"
(2) Use the dip switches to select functions.
Select the function required for each input/output channel to be used.
The switch assignment for each channel is shown below. Configure each of the settings while referring to "9. Dip Switch Functions ".
• | For channel 1, select one of the following four types: Pt100 detection, 4 to 20 mADC, 1 to 5 VDC, or 0 to 10 VDC analog input. | |||||||||
• | For channel 2, select one of the following three types: 4 to 20 mADC, 1 to 5 VDC, or 0 to 10 VDC analog input. |
|
| |||||||
(a) When using Pt100 detection (only channel 1 can be used) |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
|
| ||
| Ch | Setting | Setting Switch | Pt100 | To not use |
| ||||
|
|
|
|
|
|
|
|
|
| |
| Ch1 | Pt100 used | (1) | ON |
| OFF |
| |||
| (2) | ON |
| OFF |
| |||||
|
|
|
|
| ||||||
(b) | When using one of the analog inputs (4 to 20 mADC detection, 1 to 5 VDC detection, and 0 to 10 VDC detection) | |||||||||
|
|
|
|
|
|
|
|
|
| |
| Ch | Setting | Setting Switch | 4 to |
| 1 to | 0 to |
| To not |
|
| 20 mADC |
| 5 VDC | 10 VDC |
| use |
| |||
|
|
|
|
|
|
|
|
|
|
|
|
|
| (1) | ON |
| OFF | OFF |
| OFF |
|
| Ch1 | Setting of sensor to use | (2) | ON |
| ON | OFF |
| OFF |
|
| (3) | ON |
| ON | ON |
| OFF |
| ||
|
|
| (4) | OFF |
| OFF | ON |
| OFF |
|
|
|
| (5) | OFF |
| OFF | OFF |
| OFF |
|
|
|
| (1) | ON |
| OFF | OFF |
| OFF |
|
| Ch2 | Setting of sensor to use | (2) | ON |
| ON | OFF |
| OFF |
|
| (3) | ON |
| ON | ON |
| OFF |
| ||
|
|
|
|
|
| |||||
|
|
| (4) | OFF |
| OFF | ON |
| OFF |
|
|
|
|
|
|
|
|
|
|
|
|
(c) When using upper/lower limit alarm interlock output |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
| |||||
| Ch | Setting | Setting Switch | To use | To not use |
| ||||
|
|
|
|
|
|
|
| |||
| Ch1 | Usage of upper/lower limit alarm interlock output | (1) | ON |
| OFF |
| |||
|
|
|
|
|
|
|
| |||
| Ch2 | Usage of upper/lower limit alarm interlock output | (1) | ON |
| OFF |
| |||
|
|
|
|
|
|
|
|
|
|
|
(d) Measurement data backup interval setting (for servicing) |
|
|
|
|
|
|
|
| ||
|
|
|
|
|
|
|
| |||
| Ch | Setting | Setting Switch | 1 min |
| 2 min | 5 min |
| 10 min |
|
|
|
|
|
|
|
|
|
|
|
|
| Common | Measurement data backup interval setting | (1) | OFF |
| OFF | ON |
| ON |
|
| (2) | OFF |
| ON | OFF |
| ON |
| ||
|
|
|
|
|
|
10