4-2. External Dimensions

 

)

26

/32

11

 

(

46 (113/16)

200(77/8) 150 (529/32)

 

 

 

 

4.5

 

 

 

 

 

 

(3/16)

 

 

 

Al controller

 

 

 

 

 

 

PAC-YG63MCA

 

 

 

 

 

 

 

 

[ OUTPUT ] Non-voltage Contact Output

 

 

 

 

 

Ch1

Ch2

 

 

 

 

 

Alarm

Alarm

 

 

 

[ Output LEDs ]

 

 

 

 

 

Ch1

Ch2

 

 

 

 

 

Alarm

Alarm

 

 

 

 

 

 

 

 

N623

)

)

 

 

 

 

/32

 

 

 

Al controller

/4

 

 

 

411

(43

 

 

 

MODEL PAC-YG63MCA

 

 

 

SERVICE REF. PAC-YG60MCA-J

110 (

120

 

 

 

INPUT VOLTAGE

DC24V;0.2A

This device complies with Part15 of the FCC Rules.Operation is

 

WEIGHT

0.6 kg / 13/8 lb

subject to the following two conditions: (1)this device may not cause

SERIAL No.

 

harmful interference, and (2)this device must accept any interference

 

 

 

 

received, including interference that may cause undesired operation.

MADE IN JAPAN

 

 

 

[ INPUT ]

Ch1

Ch2

 

[ 24 VDC Power Supply]

 

 

 

 

 

 

 

Pt100

4 to 20 mA / 1 to 5 V / 0 to 10 V 4 to 20 mA / 1 to 5 V / 0 to 10 V

 

 

 

 

26 (11/32)

83.5 (35/16)

 

 

27 (13/32)

 

 

 

 

 

)

 

)

26

/32

 

32/

15

(19

(11

45(125/32) 9 (3/8)

Unit: mm (in)

5Example of System Configuration

Centralized control line

Power supply unit

PAC-SC50KUA

(1)Channel 1 temperature or humidity sensor input

(2)Channel 2 temperature or humidity sensor input

(3)Channel 1 upper/lower limit alarm output

(4)Channel 2 upper/lower limit alarm output <Restrictions>

Maximum of 50 units per G(B)-50A

However, the number of units that can be connected to a G(B)-50A is up to 50 including this device, an indoor unit, LOSSNAY unit, etc.

M-NET

G-50A or GB-50A

TB7

LAN

AI controller

M-NET

Indoor control line

 

 

 

 

 

 

TB3

 

 

 

 

 

 

 

 

 

 

AI controller

 

24 VDC Power

 

 

 

 

CITY MULTI

 

 

Supply

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(3)

(4)

 

 

 

24 VDC Power

 

(1)

(2)

 

 

 

 

 

Temperature sensor,

Upper/lower limit

 

Supply

 

 

humidity sensor,

 

alarm interlock

 

 

 

 

 

 

G(B)-50A Web or TG-2000A (1) (2)

(3) (4)

etc.

devices, etc.

Temperature sensor,

Upper/lower limit

 

humidity sensor,

alarm interlock

* This figure omits the power supply line and only shows the transmission line.

etc.

devices, etc.

Note:

For the shield ground of the M-NET centralized control line, use single-point grounding at the power unit for the transmission line.

However, when supplying electric power to the M-NET centralized control line from the R410A series outdoor unit without using a power supply unit for the transmission line, use single-point grounding at the TB7 of that outdoor unit. Furthermore, when connecting the M-NET transmission line of this device to the M-NET indoor control line, use grounding at the TB3 for each outdoor unit system.

If the M-NET transmission line of this device is connected to an M-NET indoor control line and the outdoor unit is down because, for example, the power supply is interrupted for servicing or there is a failure, the AI controller cannot be set and monitored from the system controller.

The sensor connected to the AI controller can only be monitored from G(B)-50A Web browser and TG-2000A. The sensor cannot be monitored from the G-50A LCD.

3

Page 4
Image 4
Mitsubishi Electronics PAC-YG63MCA instruction manual External Dimensions, Example of System Configuration