2Usage

The AI controller measures temperature and humidity; it also has an alarm capability if the measurement data exceeds defined setpoints. Historical measurement data can be displayed via only the G(B)-50A Web browser and TG-2000A. Temperature and humidity cannot be displayed on the G-50A LCD.

Furthermore, an alarm can be output if measurement data exceeds a preset upper or lower limit.

The AI controller also features a function that interlocks M-NET devices for indoor units, etc. set in advance and performs settings such as temperature control and operation/stoppage using measurement data values.

Caution: Usage Restrictions

Mitsubishi Electric does not take financial responsibility for damages caused by issues beyond our control or special circumstances (predicable or unpredictable); and secondary or accidental damages, and damages to other objects. We also do not take financial responsibility for opportunities lost as a result of device failure, or electrical power failure at the end- user site.

Mitsubishi Electric does not take financial responsibility caused by end-users' requests including, but not limited to, device testing, startup, readjustment and replacement.

Do not use this device in disaster prevention security or "critical to life" applications.

3Parts List

• The following parts should be included in your shipment:

Number

Part Name

Quantity

 

 

 

1

AI controller

1

2

Installation/instruction manual (this document)

1

*In addition to the parts listed above, see your local Mitsubishi Electric dealer to purchase the other parts necessary to operate this device (Refer to section 6-1). Furthermore, depending on the application, other Mitsubishi Electric parts may be required.

For details, refer to "6. Installation".

4Specifications

4-1. Device Specifications

Item

Power

Supply

Interface

Interlock

Function

Environment Conditions

Dimensions

Weight

Time Backup

During Power

Failure

Installation Environment

Description

24 VDC±10%: 5 W

 

 

 

 

 

Screw terminal

 

 

 

 

 

block (M3) (*5)

 

 

 

 

 

 

 

 

 

M-NET communication

17 to 30 VDC (*1)

 

 

Screw terminal

 

 

block (M3) (*5)

 

 

 

 

 

 

 

 

 

 

Ch

 

Sensor

Measurement

 

Measurement

 

Measurement error

External

 

 

target

 

range

 

connection method

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pt100

 

 

-30 to 60°C

 

±0.3%FS ±0.1°C (0.18°F)

Screwless terminal

 

 

 

Temperature

 

 

(*3)

 

 

(3-wire system)

 

[-22 to 140°F]

 

block (3 poles)

 

 

 

 

 

[at 25°C (77°F)]

 

Ch1

 

 

 

 

 

 

 

Input

Analog

4 to 20 mADC

 

 

 

 

±0.5%FS ±0.1°C (0.18°F)

 

 

 

Temperature/

 

(Set by system

 

(*3)

Screwless terminal

 

 

 

1 to 5 VDC

 

 

 

 

 

humidity

 

controller)

 

±0.5%FS ±0.1%RH

block (2 poles)

 

 

 

0 to 10 VDC

 

 

 

 

[at 25°C (77°F)]

 

 

 

Analog

4 to 20 mADC

 

 

 

 

±0.5%FS ±0.1°C (0.18°F)

 

 

 

 

Temperature/

 

(Set by system

 

(*3)

Screwless terminal

 

Ch2

 

1 to 5 VDC

 

 

 

 

humidity

 

controller)

 

±0.5%FS ±0.1%RH

block (2 poles)

(*2)

 

 

0 to 10 VDC

 

 

 

 

[at 25°C (77°F)]

 

Output

Upper/lower limit

 

Applied load

 

 

 

 

MIN: 5 VDC, 2 mW

block (M3.5) (*5)

(non-voltage contact)

 

 

alarm interlock output

 

MAX: 24 VDC, 5 W

Screw terminal

 

 

 

 

 

 

 

 

 

 

 

 

* AC loads cannot be connected.

 

Interlock M-NET devices according to measurement data values. (*4)

 

Temperature

 

Operating temperature range

 

0 to 40°C [32°F to 104°F]

 

 

 

 

 

Storage temperature range

 

-20 to 60°C [-4°F to 140°F]

 

 

 

 

 

 

 

Humidity

 

 

30 to 90%RH (no condensation)

 

 

 

200 (W) × 120 (H) × 45 (D) mm / 77/8 (W) × 43/4 (H) × 125/32 (D) in

0.6 kg / 13/8 lb

In the event of power failure or shut-off, the internal capacitor will continue to track time for approximately one week. (The internal capacitor takes about 24 hours to fully charge; a replacement battery is not necessary.)

Inside a control panel (indoors)

* Use this product in a hotel, a business office environment or similar environment.

*1: Supply electric power from a power supply unit for the transmission line or an outdoor unit. Furthermore, the power consumption factor of the M- NET circuitry of this unit is "1/4" (equivalent to one ME Remote Controller).

*2: Configure the dip switch settings for the analog input method to use while referring to "9. Dip Switch Functions".

*3: The measurement error for the system includes the measurement error for this unit, sensor, and wiring. a%FS (full scale) = a% × ([measurement range's upper limit value] - [lower limit value])

*4: Settings for the interlock function are performed from the Maintenance Tool. For details, refer to the operation manual for the Maintenance Tool.

*5: M3 and M3.5 are sizes of the screw on the terminal block (ISO metric screw thread). The number indicates the screw diameter (mm).

2

Page 3
Image 3
Mitsubishi Electronics PAC-YG63MCA instruction manual Usage, Parts List, Specifications Device Specifications