7-4. Connecting Alarm Setpoint Outputs (Non-valtage Contacts)

The maximum wire length is 100 m. However, since the use of long wires makes the device susceptible to noise, using wires no more than 10 m long is recommended.

To use these, various settings need to be configured. Refer to "8. Initial Settings".

 

Load

 

 

Power supply

 

 

V1 (DC)

 

X1

Power supply

Field

V2 (DC)

 

 

Connections

CN03

Ch1

Ch2

Device

 

side

Upper/lower

Upper/lower

limit alarm

limit alarm

Tightening torque for terminal screws: 1 N·m.

*The contact of the internal relay is always ON during detection of an upper/lower limit alarm. (Level output)

Caution:

To use X1 relay, obtain one that satisfies the following specifications.

Operating coil [Applied load]

MAX: 24 VDC, 5 W (Built-in diode)

MIN: 5 VDC, 2 mW (Built-in diode)

*1 AC loads cannot be connected.

*2 Provide a power supply (V1, V2) that matches the load and relay to be used.

To drive a direct load, use ones within the following. [Applied load]

MAX: 24 VDC, 5 W

MIN: 5 VDC, 2 mW

*AC loads cannot be connected.

Make sure that the copper wiring is not short-circuiting the plates (cover, lower case) or neighboring wires.

Perform wiring so that the terminal block is not strained. If strained, use a wire guide or junction terminal to alleviate the stress on the terminal block.

Do not connect the wires directly from the top of the control panel to the terminal block.

Moisture may enter this device along the wiring and cause electric shock or fire.

9

Page 10
Image 10
Mitsubishi Electronics PAC-YG63MCA instruction manual Connecting Alarm Setpoint Outputs Non-valtage Contacts