Internal 33CSUCE-06 relay contacts are rated for 1 amp/24 vac.

*To control heating device and provide automatic indoor- fan operation on heating.

²Jumper removed only when separate 24-v trans- former power source is used to power the 33CSUCE-06 relay pack.

**Field-supplied.

NOTES:

1.Liquid line solenoid valves LLS-A1 and A2 are used for solenoid drops.

2.Solenoid drop is a safety feature which prevents refrigerant migration to the compressor during the OFF cycle. It is recommended on all systems and required on systems where piping exceeds 75 ft (22.9 m) in length.

3.The 33CSUCE-01 relay pack requires 10 va.

4.Factory wiring is in accordance with NEC; ®eld modi- ®cations or additions must be in compliance with all applicable codes.

5.Wiring for ®eld power supply must be rated 75 C minimum. Use copper, copper-clad aluminum, or aluminum conductors. Maximum incoming wire size for each terminal block is 500 kcmil.

6.Terminal blocks are for external ®eld control con- nections. Control connections are to be Class 1 wiring.

7.Field-supplied components (IFC, LLS-A1, and LLS-A2) must have a maximum sealed coil rating of 30 va each (0.25 amp at 120 vac and 0.13 amp

at 230 vac). Thermostats must have a minimum pilot duty rating of 300 va (2.5 amps at 120 vac and

1.3amps at 230 vac).

8.Replacement of factory wires must be with type 105 C wire or its equivalent.

9.Field-supplied liquid line solenoid valves installed at the evaporator are required on all units.

10.Units have 175 va of power available for ®eld- installed accessories.

11.To minimize voltage drop, the following wire sizes are recommended:

LENGTH Ð

INSULATED WIRE Ð AWG

Ft (M)

(35 C Minimum)

Up to 50

No. 18

(15.2)

 

50-75

No. 16

(15.2-22.9)

 

More Than 75

No. 14

(22.9)

 

 

 

LEGEND

AWG

Ð American Wire Gage

CR

Ð Control Relay

HD

Ð Heating Device

IFC

Ð

Indoor-Fan Contactor

IFR

Ð

Indoor-Fan Relay

kcmil

Ð

Thousand Circular Mils

LLS

Ð

Liquid Line Solenoid

NEC

Ð National Electrical Code

 

 

(U.S.A. Standard)

RÐ Heating Relay (®eld- supplied 24-v sealed coil,

RV

Ð

10 va maximum rating)

Reversing Valve

TB

Ð

Terminal Block

 

 

Factory Wiring

 

 

Field Wiring

Fig. 21 Ð Field Wiring, One 2-Stage Thermostat Ð 38AH044-084 Optional Single-Circuit Units