Step 4 Ð Make Electrical Connections

Step 4 Ð Make Electrical Connections

POWER SUPPLY Ð Electrical characteristics of available power supply must agree with unit nameplate rating. Supply voltage must be within the limits shown in Tables 10A or 10B, 11 and 12. See Table 13 for control circuit data and Table 14 for fan motor electrical data.

IMPORTANT: Operation of unit on improper supply voltage or with excessive phase imbalance constitutes abuse and can affect any Carrier warranty.

FIELD POWER CONNECTIONS Ð All power wiring must comply with applicable local and national codes. Install ®eld- supplied, branch circuit safety disconnect(s) of a type that can be locked off/open. Disconnects must be located within sight of, and readily accessible from, the unit in compliance with NEC (National Electrical Code) (U.S.A. Standard) Article 440-14.

All ®eld power enters the unit through a hole in the con- trol box shelf. Refer to Fig. 20-28 for ®eld wiring details.

MAIN POWER Ð Units 38AH044-104 have single-point power connection to simplify ®eld-power wiring (all power enters at one end). Units 38AH124 and 134 require 2 con- nection points, one for each module. Units may use copper, copper-clad aluminum, or aluminum conductors at all volt- ages. The maximum wire size units can accept per terminal block is 500 kcmil.

Power must be supplied as shown in Table 15.

CONTROL CIRCUIT WIRING Ð Control circuit wiring is accomplished with a step-down transformer on voltage des- ignations 500, 600, and 100 in table below where the pri- mary voltage is ®eld voltage. For 208/230-v, 3-ph, 60-Hz units, ensure that the transformer primary is wired properly for the voltage which will be applied. All control wiring must comply with applicable local and national codes. The safety circuits are 24 v on all units. The safety circuit voltage is created with a step-down transformer where main control voltage is the transformer primary voltage.

See Table 13 for control circuit information.

Table 10A Ð Electrical Data Ð 50/60 Hz (38AH044-084 Dual-Circuit Units)

 

 

 

STANDARD UNIT

 

 

 

 

 

COMPRESSOR*

 

 

Voltage

Compressor

Nameplate

Supply Voltage²

 

 

 

A1

B1

 

38AH

A1/B1

 

 

MCA

MOCP

ICF

 

 

 

 

 

 

 

Designation

Model No.

V-Ph-Hz

Min

Max

 

 

 

RLA

 

LRA

RLA

 

LRA

 

 

 

 

 

 

 

 

 

500

 

208/230-3-60

187

254

179.4

225

434.7

67.9

 

345

67.9

 

345

 

600

 

460-3-60

414

508

91.3

100

218.6

34.6

 

173

34.6

 

173

044

100

 

575-3-60

518

632

78.4

100

162.4

28.8

 

120

28.8

 

120

200

06E4250/250

380-3-60

342

418

93.5

125

241.2

34.6

 

191

34.6

 

191

 

800 (PW)

 

230-3-50

198

254

180.2

225

296.7

67.9

 

207

67.9

 

207

 

900

 

380/415-3-50

342

440

91.5

100

219.6

34.6

 

173

34.6

 

173

 

300 (PW)

 

346-3-50

325

367

100.0

125

165.9

33.3

 

115

33.3

 

115

 

500

 

208/230-3-60

187

254

206.6

250

535.7

67.9

 

345

89.7

 

446

 

600

 

460-3-60

414

508

102.4

125

268.6

34.6

 

173

43.6

 

223

054

100

06E4250/265

575-3-60

518

632

88.0

125

206.4

28.8

 

120

36.5

 

164

200

380-3-60

342

418

107.1

150

297.2

34.6

 

191

45.5

 

247

 

 

 

 

 

900

 

380/415-3-50

342

440

102.7

125

269.6

34.6

 

173

43.6

 

223

 

300 (PW)

 

346-3-50

325

367

107.0

150

198.9

33.3

 

115

44.9

 

148

 

500

 

208/230-3-60

187

254

249.3

350

617.5

89.7

 

446

106.4

 

506

 

600

 

460-3-60

414

508

115.5

150

307.6

43.6

 

223

46.8

 

253

064

100

06E8265/275

575-3-60

518

632

100.6

125

226.1

36.5

 

164

40.4

 

176

200

380-3-60

342

418

126.9

175

341.1

45.5

 

247

52.6

 

280

 

 

 

 

 

900

 

380/415-3-50

342

440

114.1

150

335.6

43.6

 

223

46.8

 

280

 

300 (PW)

 

346-3-50

325

367

129.8

175

230.5

44.9

 

148

53.8

 

168

 

500

 

208/230-3-60

187

254

330.5

450

829.0

106.4

 

506

147.4

 

690

 

600

 

460-3-60

414

508

148.6

200

408.2

46.8

 

253

65.4

 

345

074

100

06E8275/299

575-3-60

518

632

132.2

175

336.8

40.4

 

176

57.1

 

276

200

380-3-60

342

418

174.5

250

458.0

52.6

 

280

78.8

 

382

 

 

 

 

 

900

 

380/415-3-50

342

440

143.0

200

403.8

46.8

 

280

65.4

 

345

 

300 (PW)

 

346-3-50

325

367

170.8

250

300.4

53.8

 

168

79.5

 

229

 

500

 

208/230-3-60

187

254

371.5

500

870.0

147.4

 

690

147.4

 

690

 

600

 

460-3-60

414

508

167.2

225

426.8

65.4

 

345

65.4

 

345

084

100

06E8299/299

575-3-60

518

632

148.9

200

353.5

57.1

 

276

57.1

 

276

200

380-3-60

342

418

200.7

250

484.2

78.8

 

382

78.8

 

382

 

 

 

 

 

900

 

380/415-3-50

342

440

167.6

225

428.4

65.4

 

345

65.4

 

345

 

300 (PW)

 

346-3-50

325

367

205.3

250

334.9

79.5

 

229

79.5

 

229

See page 24 for Legend and Notes.