Chart 1, Field Power Supply Connections
UNIT | VOLTAGE | Hz | DIAMETER | QUANTITY | ||
38AH | (in.) | |||||
|
|
| ||||
| 208/230 | 60 | 35¤8 | (92) | 1 | |
124A | 460, 575, | 60 | 21¤2 | (63) | 1 | |
124B | 380 | |||||
|
|
|
| |||
| 346, 380/415 | 50 | 35¤8 | (92) | 1 |
LEGEND
CÐ Copper Fin Coils MTG Ð Mounting
SAE Ð Society of Automotive Engineers
NOTES:
1. The approximate operating weight of the unit is:
7260 lb (3293 kg) | |
8126 lb (3686 kg) |
2.Unit must have clearances for air¯ow as follows: Top Ð Do not restrict in any way.
Ends Ð 5 ft [1524 mm] Sides Ð 6 ft [1829 mm]
3.Mounting holes may be used to mount unit to concrete pad. They are not rec- ommended for mounting unit to spring isolators.
4.One 35¤8
5.Circled numerals in Top View refer to condenser fans by position.
6.If spring isolators are used, a perimeter support channel between the unit and the isolators is recommended. Do not support each module separately.
7.Each module of the unit must be rigged into position separately. The unit must not be rigged after modules have been connected.
8.Suction and liquid connections can exit on either side of the unit.
9.Field power supply connections are required for each module.
10.See Table 1 for rigging center of gravity (Dimensions K,L,X,Y). See Table 2A and 2B for
Fig. 5 Ð Dimensions Ð Unit 38AH124