Units 38AH124 and 134 Piping Kit Connections Ð The 38AH124 and 134 units are delivered with a factory- supplied suction and liquid piping kit for installation in the
Remove the copper tubes from Module 124A or 134A com- pressor rails. Save the pipe clamps for later use. Cut the
NOTE: Piping kit is designed to allow air handler connec- tions to project from either side of the service space.
To prepare condensing unit modules for piping connec- tion, refer to beginning paragraphs of Step 3 Ð Make Refrigeration Piping Connections, page 14.
Two
Protect liquid valves from the heat of brazing.
Braze the piping connections.
Level the tubes and clamp to the corner posts with factory- supplied
Units 38AH124 and 134 Sheet Metal Trim Kit Installation
ÐAfter the units are in place and the piping kit is installed, install the sheet metal trim kit.
NOTE: Install sheet metal trim kit before connection to air handler tubing in case the modules must be repositioned to accommodate the sheet metal installation.
Remove two
Attach Top Cover Ð To attach top cover, proceed as follows:
For Unit 38AH124, remove screws A from top of each of 4 corner posts at service space. See Fig. 18. Place cover on top of service space and align top cover slots with corner post screw holes. Reinsert screws A.
For Unit 38AH134, remove screws A from top of each cor- ner post on Module 134A and screws B from top of each corner post on Module 134B. See Fig. 18. Top cover is in 2 pieces: one vertical piece and one horizontal piece. Slide vertical top cover partly under Module 134B end cover flange;
align holes and reinsert screws B. Place horizontal cover on top of Module 134A end cover with opposite side resting on the horizontal ¯ange of the installed Module B vertical top cover piece. Align holes on ¯ange and top cover. Reinsert screws A through the top cover holes into the end cover. From within the service space, insert supplied screws up through the ¯ange and horizontal cover to make a secure connection between the horizontal and vertical cover pieces.
Insert supplied screws into each of the 2 holes in the ver- tical side ¯ange of the top cover at each end of the service space.
Attach Side Panels Ð Insert side panels at the ends of the service space and hook side panel ¯ange over the 2 screws previously inserted in the top cover ¯ange. Fasten panels to the corner posts with supplied
Connect Tubing from Evaporator to Unit
Protect liquid valves from the heat of brazing.
Braze the liquid and suction lines from the evaporator to the condensing unit liquid and suction lines. Leak test the entire system by the pressure method described in the Carrier Standard Service Techniques Manual, Chapter 1, Section
NOTES:
1.Ensure suction tube is level for oil return requirements.
2.Protect liquid valves from heat of brazing.
Fig. 16 Ð Units 38AH124 and 134 with Installed
Piping Kit
21