Fig. 2 Ð Dimensions Ð Units 38AH074,084

 

 

DUAL CKT

 

SINGLE CKT

 

 

 

 

 

SUCTION

21¤8

Dia [54 mm]

25¤8

Dia [67 mm]

CONNECTION(S)

 

 

 

 

 

 

 

LIQUID

 

7¤8

Dia [22 mm]

11¤8

Dia [29 mm]

CONNECTION(S)

 

 

 

 

 

 

 

SUCTION C

2

-11¤16

[627mm]

1

-105¤16[567mm]

LIQUID D

1

-101¤16

[561mm]

1

-105¤16[567mm]

SUCTION (Ckt A)

1

-713¤16[503mm]

2

-5¤8

[626mm]

SUCTION (Ckt B)

2

-5¤8

 

[626mm]

 

 

Ð

LIQUID (Ckt A)

2

-53¤4

[756mm]

2

-105¤8[879mm]

LIQUID (Ckt B)

2

-105¤8

[879mm]

 

 

Ð

Chart 1, Field Power Supply Connections

UNIT

VOLTAGE

Hz

DIAMETER Ð in. [mm]

QTY

074

208/230

60

21¤2 [63]

2

460

60

21¤2 [63]

1

 

 

346, 380/415

50

35¤8 [92]

1

074, 084

380

60

35¤8

[92]

1

 

575

60

21¤2

[63]

1

084

208/230

60

35¤8

[92]

2

460

60

35¤8

[92]

1

 

LEGEND

CÐ Copper Fin Coils MTG Ð Mounting

SAE Ð Society of Automotive Engineers

NOTES:

1. The approximate operating weight of the unit is:

38AH-074---

3812 lb (1729 kg)

38AH-074--C

4229 lb (1918 kg)

38AH-084---

4057 lb (1840 kg)

38AH-084--C

4735 lb (2148 kg)

2.Unit must have clearances for air¯ow as follows: Top Ð Do not restrict in any way.

Ends Ð 5 ft [1524 mm] Sides Ð 6 ft [1829 mm]

3.Mounting holes may be used to mount unit to concrete pad. They are not recommended for mounting unit to spring isolators. If spring isolators are used, a perimeter support channel between the unit and the iso- lators is recommended.

4.See Table 1 for rigging center of gravity (Dimensions X,Y). See Table 2A and 2B for A-D corner weights.

5.Circled numerals in Top View refer to condenser fans by position.

Fig. 2 Ð Dimensions Ð Units 38AH074,084

5