Carrier 38AH044-084 specifications

Models: 38AH044-084

1 56
Download 56 pages 61.81 Kb
Page 28
Image 28
Manual background

Internal 33CSUCE-06 relay contacts are rated for 1 amp/24 vac.

*To control heating device and provide automatic indoor- fan operation on heating.

²Jumper removed only when separate 24-v trans- former power source is used to power the 33CSUCE-06 relay pack.

**Field-supplied.

NOTES:

1.Liquid line solenoid valve LLS-A is used for so- lenoid drop on circuit A. Liquid line solenoid valve LLS-B is used for solenoid drop for circuit B.

2.Solenoid drop is a safety feature which pre- vents refrigerant migration to the compressor dur- ing the OFF cycle. It is recommended on all systems and required on systems where piping exceeds 75 ft (22.9 m) in length.

3.The 33CSUCE-06 relay pack requires 10 va.

4.Factory wiring is in accordance with NEC; ®eld modi®cations or additions must be in compli- ance with all applicable codes.

5.Wiring for ®eld power supply must be rated 75 C minimum. Use copper, copper-clad alumi- num, or aluminum conductors. Maximum in- coming wire size for each terminal block is 500 kcmil.

6.Terminal blocks TB3 and TB4 are for external ®eld control connections. Control connections are to be Class 1 wiring.

7.Field-supplied components (IFC, LLS-A, and LLS-B) must have a maximum sealed coil rat- ing of 30 va each (0.25 amp at 120 vac and

0.13 amp at 230 vac). Thermostats must have a minimum pilot duty rating of 300 va (2.5 amps at 120 vac and 1.3 amps at 230 vac).

8.Replacement of factory wires must be with type 105 C wire or its equivalent.

9.Field-supplied liquid line solenoid valves installed at the evaporator are required on all units.

10.Units have 175 va of power available for ®eld- installed accessories.

11.To minimize voltage drop, the following wire sizes are recommended:

LENGTH Ð

INSULATED WIRE Ð AWG

Ft (M)

(35 C Minimum)

Up to 50

No. 18

(15.2)

 

50-75

No. 16

(15.2-22.9)

 

More Than 75

No. 14

(22.9)

 

 

 

LEGEND

AWG

Ð American Wire Gage

CR

Ð Control Relay

HD

Ð Heating Device

IFC

Ð

Indoor-Fan Contactor

IFR

Ð

Indoor-Fan Relay

kcmil

Ð

Thousand Circular Mils

LLS

Ð

Liquid Line Solenoid

NEC

Ð National Electrical Code

 

 

(U.S.A. Standard)

RÐ Heating Relay (®eld- supplied 24-v sealed coil,

RV

Ð

10 va maximum rating)

Reversing Valve

TB

Ð

Terminal Block

 

 

Factory Wiring

 

 

Field Wiring

Fig. 20 Ð Field Wiring, One 2-Stage Thermostat Ð 38AH044-084 Dual-Circuit Units

28

Page 28
Image 28